![Omron CVM1D Operation Manual Download Page 310](http://html1.mh-extra.com/html/omron/cvm1d/cvm1d_operation-manual_742532310.webp)
0000
00
(096)
INBL
0500
(097)
DCBL
1200
0000
00
305
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
EQ (A50006):
The result is 0.
N (A50008):
Shows the status of bit 15 of Wd+1 after execution.
Example
When CIO 000000 is ON in the following example, the content of CIO 0500 and
CIO 0501 is incremented by 1 as a binary value.
Address
Instruction
Operands
00000
LD
000000
00001
INBL(096)
0500
Wd+1: CIO 0501
Wd: CIO 0500
+ 1
0
0 0 0 0
F F F F
Wd+1: CIO 0501
Wd: CIO 0500
0 0 0 1
0 0 0 0
N
5-22-8 DOUBLE DECREMENT BINARY: DCBL(097)
(097)
DCBL Wd
Wd: Word
CIO, G, A, DM
Operand Data Area
Ladder Symbol
Variations
j
DCBL(097)
When the execution condition is OFF, DCBL(097) is not executed. When the ex-
ecution condition is ON, DCBL(097) decrements the 8-digit binary number con-
tained in Wd+1 and Wd, without affecting carry (CY). Wd+1 contains the 16
4
,
16
5
, 16
6
, and 16
7
digits.
Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
EQ (A50006):
The result is 0.
N (A50008):
Shows the status of bit 15 of Wd+1 after execution.
Example
When CIO 000000 is ON in the following example, the content of CIO 1200 and
CIO 1201 is decremented by 1 as a binary value.
Address
Instruction
Operands
00000
LD
000000
00001
DCBL(097)
1200
Wd+1: CIO 1201
Wd: CIO 1200
Wd+1: CIO 1201
Wd: CIO 1200
0 0 0 1
0 0 0 0
0 0 0 0
F F F F
– 1
0
N