5. Peripheral Connector
This connector is used to connect a Programming Device such as a comput-
er running SSS or a Programming Console. The baud rate depends upon
the Programming Device that is connected, so be sure to set the baud rate
on the Communications DIP Switch. (See below.)
6. Communications DIP Switch
Sets the CPU Unit’s communications specifications.
Pin number(s)
Position
Function
1, 2
---
Pins 1 and 2 set the baud rate for the peripheral
connector. Set the baud rate to 50,000 bps for a
Programming Console or 9,600 bps for a per-
1
2
Programming Console or 9,600 bps for a per
sonal computer running SSS.
OFF
OFF
Programming Device communications:
50,000 bps
ON
OFF
Programming Device communications:
19,200 bps
OFF
ON
Programming Device communications:
9,600 bps
ON
ON
Programming Device communications:
4,800 bps
3
OFF
Communicate via Host Link communications
ON
Communicate with PT (Programmable Terminal)
via NT Link communications.
4
OFF
Host link communications governed by PC Set-
up. (Effective only when pin 3 is OFF.)
ON
Initializes host link communications specifica-
tions to the following settings when connecting a
personal computer.
(Effective only when pin 3 is OFF.)
Baud rate: 9,600 bps
Unit number 00
Even parity
7-bit data
2 stop bits
5
OFF
Not used. (Leave this pin set to OFF.)
6
---
Sets the termination resistance for RS-422 com-
munications. (This setting is not used for
RS-232C communications. Leave OFF when
using RS-232C communications.)
OFF
Termination resistance OFF.
ON
Termination resistance ON.
7. Host Link Communications Selector
Set the switch to the communications specification desired for the host link
connector.
8. Host Link Connector
This connector is used for RS-232C or RS-422 communications. Select
RS-232C or RS-422 communications with the host link communications se-
lector (7). The PERIPHERAL/HOST LINK indicators indicate whether a de-
vice is connected to the left or right CPU Unit.
Duplex Unit Switch Settings
Section 2-2