444
Name
Operation
D:Startup processing
Designate whether the user program (AUTOEXEC.OBJ) is automatically
transferred from the Memory Card to PC memory when the power is turned ON.
If this parameter is set to transfer the program, the program will be transferred
regardless of the PC’s startup mode setting. Changes to this setting are effective
the next time the power is turned ON.
DIP switch pin #5 on the CPU can be turned ON to transfer both the user
program (AUTOEXEC.OBJ) and the PC setup (AUTOEXEC.STD). Refer to
information on the Memory Card for details.
(Default: Don’t transfer)
E:I/O refresh
This setting is fixed at “cyclic refreshing” in CVM1D PCs.
F:Execute
control 1
Detect low battery
Designate whether battery errors are detected. Changes to this setting are
effective immediately.
(Default: Detect)
The following bits will be turned ON when a battery error is detected.
A40204 Battery Low Flag (PC or Memory Card)
A42614 Memory Card Battery Low Flag
A42615 PC Battery Low Flag
Error on power off
This setting is fixed at “Not an error” in CVM1D PCs.
CPU standby
Designate whether PC operation will begin or the CPU will standby during
initialization and until SYSMAC BUS/2 terminators are properly detected. If this
parameter is set for operation, PC operation will continue even if SYSMAC BUS/2
terminators aren’t detected. Changes to this setting are effective immediately.
(Default: CPU standby)
Measure CPU-bus
Unit (CPU SIOU)
cycle
Designate whether or not the time between CPU-bus Unit services is to be
measured. If measured, the cycle is stored starting at A310. Changes to this
setting are effective immediately.
(Default: Don’t measure cycle)
G:Execute
control 2
Execute process
This setting is fixed at “synchronous operation” in CVM1D PCs.
(This setting will be changed to “asynchronous” when the PC Setup is initialized
with SSS, but the setting is ignored in CVM1D operation.)
I/O interrupts
Not applicable in CVM1D PCs.
Power OFF interrupt
This setting is fixed at “No power OFF interrupt” in CVM1D PCs.
Dup action process
SFC instructions are not used in CVM1D PCs.
Step timer
SFC instructions are not used in CVM1D PCs.
Startup trace
Designate whether a trace is executed automatically according to the preset
conditions when the power is turned on or the operating mode is changed.
Changes to this setting are effective the next time power is turned on.
(Default: Don’t start trace.)
Indirect DM
binary/BCD
(
*
DM BIN/BCD)
Designate whether indirect DM and EM addresses are binary (PC memory
addresses) or BCD (DM and EM area addresses). Changes to this setting are
effective immediately.
(Default: BCD)
Multiple use of
JMP000
Specify whether multiple JMP000 instructions can be programmed. Changes to
this setting are effective immediately.
(Default: Multiple use of JMP000 enabled)
Comparison error
process
Designate whether or not to start operation even though an I/O verification error
has occurred. This setting affects only the start of PC operation. The I/O
verification error is non-fatal, so PC operation will continue if an I/O verification
error occurs. Changes to this setting are effective immediately.
(Default: Run after error)
PC Setup Details
Section 7-2