5-14-14 ROTATE RIGHT: ROR(063)
(063)
ROR
Wd
Wd: Word
CIO, G, A, DM, DR, IR
Operand Data Area
Ladder Symbol
Variations
j
ROR(063)
When the execution condition is OFF, ROR(063) is not executed. When the ex-
ecution condition is ON, ROR(063) shifts all Wd bits one bit to the right, shifting
CY into bit 15 of Wd and shifting bit 00 of Wd into CY.
0 1 0 1 0 1 0 0 0 1 1 1 0 0 0 1
0
Bit
15
CY
Bit
00
Use STC(078) to set CY to 1 or CLC(079) to set CY to 0 if necessary before do-
ing a rotate operation to ensure that CY contains the proper status before ex-
ecuting ROR(063).
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
CY (A50004):
Receives the status of bit 15 from Wd.
EQ (A50006):
Content of Wd is 0 after execution.
N (A50008):
Same status as bit 15 of Wd after execution.
Example
When CIO 000000 is ON in the following example, the status of CY is shifted into
bit 15 of D00010, the status of all bits within D00010 are shifted right one posi-
tion, and the status of bit 00 is shifted to CY.
Address
Instruction
Operands
00000
LD
000000
00001
ROR(063)
D00010
0
CY
LSB
MSB
1 0 1 0 1 1 0 0 1 1 1 0 0 0 1 1
0 1 0 1 0 1 1 0 0 1 1 1 0 0 0 1
1
CY
LSB
MSB
Wd: D00010
Description
Precautions
Shift Instructions
Section 5-14
0000
00
(063)
ROR D00010