446
Name
Operation
R:Watch cycle time
Designate the maximum cycle time between 10 and 40,000 ms. If the cycle time
exceeds the designated value, a fatal error will occur and A40108 will be turned
ON (Cycle Time Too Long Flag). The actual maximum cycle time might vary
about 5 ms from the designated value.
Changes to this setting are effective immediately.
(Default: 1,000 ms)
S:Error log
Designate the size and range of the error log area. When a error occurs,
information about the error is saved in this memory area together with the time
that the error occurred. The error log can be allocated in the DM or EM Area. Up
to 2,047 errors can be recorded.
Changes to this setting are effective the next time the power is turned ON.
(Default: 20 records of 5 words each in A100 to A199)
T:IOIF, RT display
Designate the display mode to be used for the 7-segment displays on I/O
Interface Units, the I/O Control Unit, and SYSMAC BUS/2 Remote I/O Slave
Units when the power is turned ON.
Changes to this setting are effective the next time the power is turned ON.
(Default: Mode 1)
7-3
PC Setup Default Settings
Parameter
Default value
A:Hold areas
H:Hold areas
CIO 1200 to CIO 1499
R:Hold bits
Nothing held.
B:Startup hold
K:Forced Status
Reset at startup.
I:I/O bits
Reset at startup.
D:Power on flag
Reset at startup. (Fixed)
C:Startup mode
PROGRAM
D:Startup processing
Don’t transfer program.
E:I/O refresh
Cyclic refreshing (Fixed)
F:Execute
l 1
B:Detect low battery
Detect
control 1
S:Error on power off
Not an error (Fixed)
T:CPU standby
CPU waits
K:Measure CPU SIOU
cycle
Don’t measure cycle.
G:Execute
control 2
C:Execute process
Synchronous (Fixed)
(This setting is changed to “asynchronous” when the PC Setup is
initialized with SSS, but the setting is ignored in CVM1D operation.)
I:I/O interrupt
Nesting
D:Power OFF interrupt
Disable (Fixed)
A:Dup action process
Error
T:Step timer
Set to 0.1 s
J:Startup trace
Don’t start trace.
B:*DM BIN/BCD
BCD
P:Multiple use of JMP000
Enabled
E:Compare error process
Run after error
H:Host link
B:Baud rate
9600 bps
S:Stop bit
2 bits
P:Parity
Even
D:Data bits
7 bits
G:Unit #
Unit number 0
I:CPU bus link
Don’t use CPU Bus Link.
J:Scheduled interrupt
Scheduled interrupts are not used in CVM1D PCs.
K:1st Rack addr (First words for local racks)
0 for CPU Rack
PC Setup Default Settings