5-15-3 DOUBLE MOVE: MOVL(032)
(032)
MOVL
S
D
D: Destination
CIO, G, A, T, C, DM
S: Source
CIO, G, A, T, C, #, DM
Operand Data Areas
Ladder Symbol
Variations
j
MOVL(032)
When the execution condition is OFF, MOVL(032) is not executed. When the ex-
ecution condition is ON, MOVL(032) copies the content of S and S+1 to D and
D+1.
S
D
Bit status
not changed.
S+1
D+1
Neither D nor S can be the last word in a data area because they designate the
first of two words.
Constants are input using eight digits.
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
Content of
*
DM word is not BCD when set for BCD.
EQ (A50006):
Content of D and D+1 are 0 after execution.
N (A50008):
Same status as bit 15 of D+1 after execution.
Example
When CIO 000005 is ON in the following example, the contents of A400 and
A401 are copied into D00200 and D00201, respectively.
Address
Instruction
Operands
00000
LD
000005
00001
MOVL(032)
A400
D00200
Before
execution
After
execution
3
A400
7
0
0
0
A401
1
F
9
3
A400
7
0
0
0
A401
1
F
9
0
D00200
0
0
0
0
D00201
0
0
0
3
D00200
7
0
0
0
D00201
1
F
9
Description
Precautions
Data Movement Instructions
Section 5-15
(032)
MOVL
A400 D00200
0000
05
Summary of Contents for CVM1D
Page 462: ...SYSMAC CVM1D Duplex System Programmable Controllers Operation Manual Revised August 2001...
Page 463: ...iv...
Page 465: ...vi...