000000
(179)
DATE D00100
342
Word
15 to 08
07 to 00
C
Minute
(00 to 59)
Second (00 to 59)
C+1
Day
(01 to 31)
Hour
(00 to 23)
C+2
Year
(00 to 99)*
Month
(01 to 12)
C+3
---
Day
(00 to 06)
00: Sunday
01: Monday
02: Tuesday
03: Wednesday
04: Thursday
05: Friday
06: Saturday
Note *Set the last two digits of the year.
Precautions
The lower limit (C) must be less than or equal to the upper limit (C+1).
An error will not be generated even if the internal clock is set to a non-existent
date (such as November 31, for example).
Note Refer to page 101 for general precautions on operand data areas.
Flags
ER (A50003):
The control word is not within the allowable range.
The content of a
*
DM word is not BCD when set for BCD.
Example
When CIO 000000 is ON in the following example, the internal clock setting will
be changed according to the content of D00100 through D00103.
Address
Instruction
Operands
00000
LD
000000
00001
DATE(179)
D00100
2
6
3
2
2
5
1
3
9
4
0
5
0
0
0
3
D00100
D00101
D00102
D00103
May 25, 1994 (Wednesday)
1:26:32
PM
5-27 Special Instructions
FAL(006) and FALS(007) are used to generate error codes and signals from the
program. IORF(184) is used to refresh specified I/O words. IODP(189) is used to
output displays on SYSMAC BUS2 Slaves, I/O Control Units, or I/O Interface
Units. EMBC(171) is used to change the EM Area bank. SRCH(164) is used to
search a specified range of words for a value.
5-27-1 FAILURE/SEVERE FAILURE ALARM: FAL(006) and FALS(007)
FAILURE ALARM: FAL(006)
(006)
FAL
N
M
M: 1
st
message wordCIO, G, A, #, DM
N: FAL number
000 to 511
Operand Data Areas
Ladder Symbol
Variations
j
FAL(006)
Special Instructions
Section 5-27