RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-49
CU A002 15A
MANTA TEST SYSTEMS
Note: The following commands are equivalent:
AIA#,0 = AIA# = AI1#,0 = AI1#
AIB#,0 = AIB#
AIC#,0 = AIC#
6.7.2.4 EXAMPLES.
Example 1: The following example simulates C-A-G fault, with prefault and postfault load, on a system
with non-zero source impedance.
The following commands should be sent (read in left to right, top to bottom order) to generate this test:
REM
FMD14 DYN
IMD5
LIN
LHM1
AAM1
PAM1
PRF1
POF1
AVA67.32,0 PHS236.2,0,2
AVA28.89,1
PHS-130.5,1,1
AVA67.32,2 PHS236.2,2,1
AVB67.32,0
PHS116.2,0,2
AVB32.55,1
PHS117.0,1,2
AVB67.32,2 PHS116.2,2,2
AVC67.32,0
PHS356.2,0,3
AVC73.62,1
PHS-3.9,1,3
AVC67.32,2 PHS245.4,2,4
AIA1.96,0
PHS245.4,0,4
AIA16.62,1
PHS172.9,1,4
AIA1,2 PHS245.4,2,4
AIB1.96,0
PHS125.4,0,5
AIB13.73,1
PHS27.7,1,5 AIB1,2 PHS125.4,2,5
AIC1.96,0
PHS5.4,0,6
AIC2.03,1
PHS-2.2,1,6 AIC1,2 PHS5.4,2,6
An STR command will initiate the fault.
MTS-1710 Settings Map Example (Individual Amplitude/Phase Mode)
Fault Type
2
Φ
−
N
Operation mode
STATIC
Freq. reference mode
LINE
Fault Phase
C-A
Current mode
I3-WYE
Harmonic
1
Amplitude adjust mode
Indiv.
Phase adjust mode
Indiv.
Parameter
PREFAULT
FAULT
POSTFAULT
ON
ON
Amplitude
Phase
Amplitude
Phase
Amplitude
Phase
VA
67.32
236.2
28.89
-
130.5
67.32
236.2
VB
67.32
116.2
32.55
117.0
67.32
116.2
VC
67.32
356.2
73.62
-3.9
67.32
356.2
IA
1.96
245.4
16.62
172.9
1.0
245.4
IB
1.96
145.4
13.73
27.7
1.0
125.4
IC
1.96
125.4
2.03
-2.2
1.0
5.4
Freq. [Hz]
-
-
-