RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-31
CU A002 15A
MANTA TEST SYSTEMS
0 - disables saving of calibration factors into NVRAM
1 - enables saving of calibration factors into NVRAM
2 - reserved for factory use only
3 - save MTS-1710 and MTS-1720 calibration factors into NVRAM
4 - reserved for factory use only
5 - reserved for factory use only
VER1
Version (MTS-1710)
•
Print Manta Test Systems MTS-1710 model number, firmware version and
serial number
VER2
Version (MTS-1720)
•
Print Manta Test Systems MTS-1720 model number, firmware version and
serial number, if it’s connected and turned on.
VER3
Status (MTS-1750)
•
Prints the MTS-1750 status code indicating the number of MTS 1750s detected.
Bits 0, 1 and 2 in the status code will have a value of 1 if an MTS-1750 is
detected corresponding to channels A, B & C. (e.g. a status code of 03 indicates
and MTS-1750 detected on channel A & B).
7 6 5 4 3 2 1 0 <- bit position
A 1 in a bit position will indicate an active warning. The bit position assignments
are as follows:
Bit# Indicator
0
1750 Detected on Ia
1
1750 Detected on Ib
2
1750 Detected on Ic
3
Incorrect number of MTS-1750’s connected for present current
mode (eg. a MTS-1750 must be connected to each of the three
current outputs if I3-wye mode is selected)
4
Invalid 1750 current mode
5, 6, 7
Factory use only
POS
Positive Phase Sequence
•
Sets positive phase sequence
NEG
Negative Phase Sequence
•
Sets negative phase sequence
FIA#
Fault Incidence Angle
•
Set fault incidence angle control
•
Valid values are 0 - 359 (degrees)
•
A value of 360 sets FIA control to random (off)