![Manta MTS-1700 SERIES Operation And Reference Manual Download Page 134](http://html1.mh-extra.com/html/manta/mts-1700-series/mts-1700-series_operation-and-reference-manual_1723616134.webp)
DETAILED OPERATION - Section 4
4-44
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
4.10.4.3 USE OF THE MULTI-SYSTEM SYNC CAPABILITY FOR TESTING PILOT-WIRE
RELAY SYSTEMS.
Pilot wire relay systems, or communications-based relay schemes, can be laboratory tested using the multi-
system sync capability of the MTS-1700 system.
FIGURE 4.28 PILOT WIRE RELAY TEST (DIRECT CONNECTION)
The MTS-1730 can be used for channel delay simulation, as shown in Figure 4.27.
For example, to simulate a 10ms channel delay, the following commands should be sent to the MTS-1730:
DIO,OCD1,1,10,1,1
DIO,OCD0,1,10,0,1
TRIP
TRIP
RELAY 1
RELAY 2
Voltage
Voltage
Current
Current
Note: Select I3-WYE current mode on both MTS-1710 systems
Multi-system
sync connection
(rear)
Tx Rx
Tx Rx
+ - + -
+ - + -
-
-
DCV
DCV
+
+
DCV
DCV
+
+
I3-WYE
I3-WYE