OPERATION SUMMARY - Section 3
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-33
CU A002 15A
MANTA TEST SYSTEMS
FIGURE 3.15 SYNCHRONIZING RELAY TEST
3.3.12.1 PHASE ANGLE LIMIT TEST.
1. Make test connections, as shown in Figure 3.15.
2. Select
Φ
-N/C-N fault mode, Il-LOW current mode. Turn
[PREFAULT] off. If the upper right corner of
the [MODE/MENU DISPLAY] doesn’t indicate “LINE”, press [FREQ] to toggle to line reference
mode.
3. Using the menu, select SETTINGS MODES FREQ SYNCHRONIZING ON to enable synchronizing
mode.
4. Turn [PREFAULT] on and, if required, check the A-N and C-N voltages by pressing [VOLTAGE], and
selecting A-N and C-N fault phase. Adjust if necessary.
GEN
(or BUS)
BUS
(or LINE)
SYNCHRONIZING
OR SYNCHROCHECK
RELAY
Va at fault frequency setting
Vc at prefault frequency setting
Select 0-N C-N fault mode and press
[PHASE] to display phase between
Vc & Va
Select variable frequency
reference mode
Select DYNAMIC operation mode
and press [FAULT] to initiate