RS-232C INTERFACE - Section 6
6-44 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
Note that the following commands are equivalent:
AVA#,0 =
AVA#
AVB#,0 = AVB#
AVC#,0 = AVC#
AI1#,0
= AI1#
6.7.1.4 EXAMPLES.
Example 1 The following example simulates a B phase fault on a non-zero source impedance system.
The following commands should be sent (read in left to right, top to bottom order) to generate this test:
REM
FMD1 DYN
IMD5
LIN
LHM1
AAM1
PAM1
PRF1
POF1
AVA67.15,0
PHS120,0,1
AVA71.95,1
PHS125.3,1,1
AVA67.15,2 PHS120,2,1
AVB67.15,0
PHS0,0,2
AVB32.84,1
PHS350.9,1,2
AVB67.15,2 PHS0,2,2
AVC67.15,0
PHS240,0,3
AVC71.05,1
PHS234.2,1,3
AVC67.15,2 PHS240,2,3
AI10,0
PHS0,0,4
AI111.75,1
PHS287.2,1,4
AI10,2 PHS0,2,4
An STR command will initiate the fault.
MTS-1710 Settings Map Example (Individual Amplitude/Phase Mode)
Fault Type
Φ
−
N
Operation
mode
Dynamic
Freq. reference mode
LINE
Fault Phase
B-N
Current mode
I3
Harmonic
1
Amplitude adjust
mode
Indiv.
Phase adjust mode
Indiv.
Parameter
PREFAULT
FAULT
POSTFAULT
ON
ON
Amplitude
Phase
Amplitude
Phase
Amplitude
Phase
VA
67.15
120.0
71.95
125.3
67.15
120.0
VB
67.15
0.0
32.84
350.9
67.15
0.0
VC
67.15
240.0
71.05
234.2
67.15
240.0
I1 or I3
0.0
0.0
11.75
287.2
0.0
0.0
I2
-
-
-
-
-
-
Freq. [Hz]
-
-
-