ADVANCED OPERATION - Section 5
5-38 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
Press [PREVIOUS] to return to the previous menu display.
To adjust/display phase angle settings in other fault states:
Press [PREVIOUS] to return to the PREFAULT, FAULT, POSTFAULT submenu display. Select the
desired state and repeat steps as outlined in this section 5.12.2.1.5.
5.12.2.2 NON-MENU CONTROL OF INDIVIDUAL PHASE.
The individual phase angles can be adjusted outside of menu control. This allows the phase angle reading
(measured) to be viewed at the same time the individual phase is changed.
To activate this method of adjustment, choose either the “Individual-voltage” or “Individual-current” phase
adjustment mode under the SETTINGS MODES PHASE INDIVIDUAL-ADJ-MODE ENABLE menu
(press [MENU] to exit). Pressing [PHASE], and turning the [MODIFY] knob, will adjust the phase of one
or more outputs, as defined by the present fault state, fault mode, current mode, and individual phase adjust
mode.
This method of adjustment changes the same settings as described in Section 5.12.2.1 above. However, this
method provides for changing the phase of more than one output at a time in
Φ
-
Φ
, 2-
Φ
-N and 3-
Φ
fault
modes. Again, there are separate prefault, fault and postfault phase settings for all outputs, and the selected
setting which is adjusted depends upon the present fault state.
When the phase adjustment mode is set to “Individual-Voltage”, the output phase which is changed is
determined by the table on the next page: