DETAILED OPERATION - Section 4
4-22
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
FIGURE 4.16 HARMONIC RESTRAINT TESTING
4.6.6.2
DC AMPS - BASIC ADJUSTMENT.
To adjust/display I2 output:
Press [CURRENT] until the upper left corner of the [MODE/MENU DISPLAY] reads “I2-AMPS”.
Turn the [MODIFY] knob as required. This adjusts the fundamental current.
OP
R1
R2
TRANSFORMER DIFFERENTIAL
RELAY
Select I2-HARMONIC
current mode.
2nd through to 10th harmonic
can be selected by pressing [FREQ]
and turning the [MODIFY] knob.
Press [CURRENT] to toggle between I2-AMPS
and %-harmonic adjustment/display