OPERATION SUMMARY - Section 3
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 3-15
CU A002 15A
MANTA TEST SYSTEMS
3.3.6 Voltage Relay Test
FIGURE 3.6 VOLTAGE RELAY TEST SETUP
3.3.6.1 PICKUP TEST.
To check the pickup level of an over/undervoltage relay:
1. Make test connections, as shown in Figure 3.6. Select
Φ
-N/A-N fault mode. If more than 150V is
required, connect the relay across A-B, and select 2
Φ
-N/A-B fault mode.