RS-232C INTERFACE - Section 6
6-8 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
AVC70
PRF1
<- prefault on
POF0
<- postfault off
DYN
<- dynamic operation mode
FMD3
<- fault mode A-B
VPR100
<- prefault amplitude at 100% of nominal
VFI35
<- fault amplitude 35% of nominal
STR
<- initiate fault
Example 3 Simple 3-
Φ
Fault
AVA70
<- set prefault
Φ
-N amplitudes to 70V
AVB70
AVC70
PRF1
<- prefault on
POF1
<- postfault on
DYN
<- dynamic operation mode
FMD7
<- fault mode 3
Φ
, monitoring Vbc
VPR100
<- prefault amplitude at 100% of nominal
VPO90.1
<- postfault amplitude at 90.1% of nominal
VFI26.8
<- fault amplitude 26.8% of nominal
STR
<- initiate fault
Example 4
Φ
-N Ramp
AVA70
<- set prefault
Φ
-N amplitudes to 70V
AVB70
AVC70
PRF1
<- prefault on
POF0
<- postfault off
DYN
<- dynamic operation mode
FMD2
<- fault mode C-N
VFI60
<- initial fault amplitude at 60V
VFF10
<- final fault amplitude at 10V
VRR23
<- ramp rate at 23V/sec
STR
<- initiate fault and ramp
Example 5
Φ
-
Φ
Ramp
FMDO
AVA70
<- set prefault
Φ
-N amplitudes to 70V
AVB70
AVC7
PRF1
<- prefault on
POF0
<- postfault off
DYN
<- dynamic operation mode
FMD5
<- fault mode C-A
VFI100
<- initial fault amplitude at 100% of nominal
VFF15
<- final fault amplitude at 15% of nominal
VRR24
<- ramp rate at 24%/sec
STR
<- initiate fault and ramp