OPERATION SUMMARY - Section 3
3-10 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
Running a dynamic test:
•
Select DYNAMIC operation mode by pressing the [STATIC/DYNAMIC] button.
•
Press [FAULT] to initiate the test. The fault levels are now applied to the outputs, and the timer is
started.
•
If, and when, the relay operates, the stop trigger will be activated, and the [STOP/RESET] button will
be lit.
The values of all parameters (V, I, f,
Φ
) will be frozen at the time of the stop trigger, and can be
recalled.
The operate time can be displayed by pressing the [TIME] button.
•
Press [STOP/RESET] to reset the MTS-1710 to the PREFAULT state.