ADVANCED OPERATION - Section 5
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 5-19
CU A002 15A
MANTA TEST SYSTEMS
High-speed peak responding measurement is useful when testing fast response solid state relays. These
relays will operate in response to fault levels before normal RMS measurement circuitry is able to accurately
measure the fault current/voltage levels. The high speed measurement mode is peak-responding and
measures the output current and voltages every cycle (for 40-75Hz outputs).
For almost all testing, the default AUTO setting is adequate. For testing involving high speed ramping, the
PEAK setting may be required to capture the value of rapidly changing currents/voltages.
5.8 DEFAULT SETTINGS
5.8.1 Restoring Default Settings
To return all settings to factory default values, select SETTINGS DEFAULT in the menu, or execute the
DEF command via the RS-232C interface.
5.8.2 Primary Default Settings
The following settings map shows the default power-up settings:
* If in manual control mode, the current mode, fault mode, fault type, fault phase and current mode
selected will be the one selected on the front panel.
MTS-1710 Default Settings Map
Fault Type
Φ
-
N*
Operation mode
STATIC
Freq. reference mode
LINE
Fault Phase
A-N*
Current mode
I1-LOW*
Harmonic
1
Parameter
PREFAULT
FAULT
POSTFAULT
OFF
Initial
Ramp Rate
Duration
Final
OFF
VAN [V]
69.3
-
-
-
-
-
VBN [V]
69.3
-
-
-
-
-
VCN [V]
69.3
-
-
-
-
-
VAN
*
[V]
69.3
0
OFF
OFF
69.3
69.3
I1 or I3 [A]
0
0
OFF
OFF
0
0
Phase [deg]
0
0
OFF
OFF
0
0
Freq. [Hz]
60.000
60.000
OFF
OFF
60.000
60.000
I2 current [A]
0
Special Modes and Settings (via menu)
I2 %harmonic
0
Timer Start Mode
INT
Fault incidence angle
0
I4 [DC amps]
0
Dynamic Meas. Mode
AUTO
Synchronizing mode
OFF
Phase Sequence
+ve
Auto-reclose delay
0.0