RS-232C INTERFACE - Section 6
6-32 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
DEF
Default settings
•
Restores all settings to power-up default values (except DC voltage)
•
See Section 5.8 for details
TDR#
Time Delay to Reclose
•
Sets the auto-reclose time delay
•
Valid values are 0 - 99.999 seconds
RIF#
Reclose into fault
•
Sets the number of reclose into fault events
•
Valid values are 0 - 11
•
Default value is 0
The [MODE/MENU DISPLAY] can be programmed to display user messages and data using the
following commands:
DRD
Display Readings Data
•
This command selects the multiple readings display to be shown on the
[MODE/MENU DISPLAY].
•
See Section 5.10.2 for a complete description of this feature.
DUD
Display User Data
•
This command selects user data to be displayed on the [MODE/MENU
DISPLAY].
UDD
User Display Data
•
This command defines up to 40 characters of user data to be displayed on the
[MODE/MENU DISPLAY].
•
The data is defined in double quote characters
•
The following example displays a user message on the [MODE/MENU
DISPLAY]:
Ready>UDD“Set fault voltage to 40V”
Ready>DUD
Ready>
DMD#
Display Mode Data
•
This command selects mode data to be displayed on the [MODE/MENU
DISPLAY].
•
The argument specifies the type of mode display. Valid values are 0 -15.
0 - Default mode display
1 - Mode display with V÷I ratio
2 - Mode display with V÷2I ratio
3 - Mode display with V÷
I ratio
4 - Mode display with V÷(I + kI) ratio (Z1gnd display)
5 - Mode display with I1÷I2 ratio
6 - Mode display with I2÷I1 ratio
3