RS-232C INTERFACE - Section 6
6-34 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
VB,069.27,240.0
VC,069.27,120.0
I1,005.04,030.0
Ready>
The first item in the line is the output. The first number is the magnitude in volts
or amps, and the second number is the absolute phase angle in degrees.
•
Note that the currents values in I3-WYE current mode, and the voltage values,
are the settings, and not measured values. The phasors, which are output, will
change, depending upon the current mode.
•
Manta Test Systems’ MTS-2100 Powerscope program uses this to produce a
real-time display of the phasors.
AXC#,#
AUX Contacts Arrangement
•
First argument sets the AUX contact output arrangement. Valid values are 0 - 5:
0 - NO contacts (default)
1 - NC contacts
2 - 52A signal simulation
3 - 52B signal simulation
4 - Permissive signal simulation (not supported by AUX CONTACT_2)
5 - Unblock signal simulation (not supported by AUX CONTACT_2)
•
Second argument (optional ) specifies the contact output. Valid values are 1 or 2.
Default value: 1 i.e. [AUX CONTACT_1]
PUD#
•
Permissive/unblock Delay
Programs the delay time for the permissive/unblock signal simulation using
the auxiliary contacts.
•
Valid values: 0.000 -20.000 seconds
•
Default value: 0.032 sec
BKT#
Breaker Time
•
Sets the breaker time
•
Valid values are 0 - 5.000 (seconds)
PFC#
Postfault Control
•
Sets postfault control features
•
Valid values are 0 - 3
0 - 3
Φ
trip type, line side PT’s
1 - 1
Φ
trip type, line side PT’s
2 - 3
Φ
trip type, bus side PT’s
3 - 1
Φ
trip type, bus side PT’s
RET#
Remote End Trip Time
•
Sets the remote end trip simulation time
•
Valid values are 0 - 20.000 (seconds)
PMM#
Phase Measurement Mode
•
Sets the phase measurement mode
•
Valid values are 0-1
0 - normal speed
1 - high speed