DETAILED OPERATION - Section 4
4-20
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
FIGURE 4.15 PURE DC RECTIFIED SIGNAL WITHOUT ANY FUNDAMENTAL CURRENT
4.6.6.1
% PURE HARMONIC - BASIC ADJUSTMENT
To adjust/display I2 output:
Press [CURRENT] until the upper left corner of the [MODE/MENU DISPLAY] reads “I2-AMPS”.
Turn the [MODIFY] knob as required. This adjusts the total RMS output, maintaining the percentage
harmonic constant.
To adjust/display %-harmonic:
Press [CURRENT] until the upper left corner of the [MODE/MENU DISPLAY] reads “%-HARM”.
Turn the [MODIFY] knob, as required. This adjusts the percentage harmonic of the output from 0 to 50%.
To adjust/display harmonic frequency:
Press [FREQ] and turn the [MODIFY] knob, as required, to select desired harmonic or frequency.
In line frequency mode, the harmonic number is displayed in the [MODE/MENU DISPLAY]. In variable
frequency mode, the harmonic frequency in Hz is displayed in the [MODE/MENU DISPLAY].
Note: Adjustment of harmonic frequency requires the %HARM to be set to something other than zero.
To adjust waveshape:
Press [PHASE] and turn the [MODIFY] knob, as required. This adjusts the “phase” between the harmonic
and the fundamental, thereby changing the waveshape of the I2-Harmonic output.
t
I
0