FAULT PLAYBACK - Section 7
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 7-11
CU A002 15A
MANTA TEST SYSTEMS
7.8 EXTERNAL DATA MODE USAGE
7.8.1 Connections
FIGURE 7.1 EXTERNAL AMP IN CONNECTOR
MTS-1710 External Amp input connector
MTS-1720 External Amp input connector
Pin #
Signal
Pin #
Signal
1
Va input
1
Ib input
2
Signal ground
2
Signal ground
3
Vb input
3
Ic input
4
Vc input
4
no connection
5
Ia input
5
no connection
6
External sync +
7
External sync -
The analog input should be connected to a low level signal source (±5V peak maximum). The amplifying
gain factors are 50 Vrms per 1 Vrms for the voltage channels and 10 Arms per 1 Vrms for the current
channels.
7.8.2 General Procedure
1. Connect the signal source to the MTS-1710 and MTS-1720.
2. Turn on the MTS-1710 and MTS-1720, and then the signal source.
3. Send the following commands to the MTS-1710:
REM
<- enter remote control mode
IMD5
<- select I3/I3-WYE current mode (IMD3 is also allowable here if only the MTS-
1710 is to be used)
FMD0
<- set a
Φ
-N fault mode to allow setting max voltages
LIN
<- Line frequency mode
AVA90
<- set the maximum
Φ
-N rms voltages expected to be output
AVB100
AVC95
RCM3
<- select external data mode fault playback
DYN
<- select dynamic operation mode to do timing
4. Initiate analog playback from the computer.
5. Press [STOP/RESET], or send the RES command to reset the MTS-1710 fault state back to prefault.
Pin 6
Pin 1
Pin 4
Pin 2
Pin 7
Pin 3
Pin 5
mp Signal Input Connectors
As
External A
viewed from rear panel of the instrument
Pin 1
Pin 4
Pin 2
Pin 3
Pin 5
MTS-1710
MTS-1720