OPERATION SUMMARY - Section 3
3-4 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
22. [AUX CONTACT 2] OUTPUT TERMINALS
These auxiliary contact terminals are closed whenever the MTS-1710 is in the FAULT state. They
may be used to slave an external device, such as a chart recorder, or to switch an additional current
or voltage.
Both contacts 1 and 2 are rated at 5A/120VAC and may be programmed for other functions (see
Section 5.15).
23. [FAULT PHASE] SELECTOR
This switch selects the phase being faulted. As well, this phase of voltage is monitored and used
for phase measurement.
24. [DC VOLTAGE ENABLE] PUSHBUTTON
This pushbutton is used to enable/disable the DC voltage output.
25. [DC VOLTAGE LIVE] LED
This LED, when on, indicates that the DC voltage output is live. Green indicates 22-70V; yellow
indicates 70-130V; and red indicates 130-300V.
26. [FAULT TYPE] SELECTOR
This knob selects the type of fault to be simulated.
27. [DC VOLTS] OUTPUT TERMINALS
DC voltage output terminals for units with the DC Voltage output option.
28. [DC AMPS] OUTPUT TERMINALS
These terminals provide DC current output in the I4 current mode.
29. [CURRENT MODE] SELECTOR
This knob selects the active current mode.
30. [REMOTE] LED INDICATOR
When lit, this LED indicates that the MTS-1710 is under remote control.
31. [I1 OUTPUT] TERMINALS
These output terminals provide output current in the I1-LOW and I1-HIGH current modes.