RS-232C INTERFACE - Section 6
6-6 MTS-1700 SERIES OPERATION AND REFERENCE MANUAL
MANTA TEST SYSTEMS
CU A002 15A
AVB#
Amplitude Vb
•
Sets the maximum prefault amplitude of Vb
•
Valid values are 0 - 150.00 (volts)
•
This command is disallowed when
Φ
-
Φ
fault type is selected. See example for
use in
Φ
-
Φ
fault mode.
AVC#
Amplitude Vc
•
Sets the maximum prefault amplitude of Vc
•
Valid values are 0 - 150.00 (volts)
•
This command is disallowed when
Φ
-
Φ
fault type is selected. See example for
use in
Φ
-
Φ
fault mode.
VPR#
Voltage - Prefault
•
Sets the prefault voltage amplitude
•
For
Φ
-N and 2-
Φ
-N fault modes, specify values in volts. Valid values are 0 -
150.00 (volts)
•
For
Φ
-
Φ
and 3-
Φ
fault modes, specify value in percent. This percentage is the
percentage of the nominal
Φ
-N voltage. Valid values are 0-100.0 (%).
•
In
Φ
-
Φ
fault modes, this percentage setting is only approximate.
•
Note that prefault must be turned on (using the PRF1 command) for this value to
be applied to the outputs in prefault state
•
Note that, for 2
Φ
-N fault modes, this setting changes the
Φ
-N values. However,
the
Φ
-
Φ
value is displayed on the MTS-1710 display.
VFI#
Voltage - Fault Initial
•
Sets the fault initial voltage
•
For
Φ
-N and 2-
Φ
-N fault modes, specify values in volts. Valid values are 0 -
150.00 (volts)
•
For
Φ
-
Φ
and 3-
Φ
fault modes, specify value in percent. This percentage is the
percentage of the nominal
Φ
-N voltages. Valid values are 0-100.0 (%).
•
In
Φ
-
Φ
fault modes, this percentage setting is only approximate.
If a VFI# command is sent while in FAULT state and dynamic operation mode,
it will only take effect immediately if all ramp rates and durations are zero.
Otherwise, a reset action, and a subsequent start trigger into FAULT state, is
required to apply the new fault initial value.
•
Note that, for 2-
Φ
-N fault modes, this setting changes the
Φ
-N values.
However, the
Φ
-
Φ
value is shown on the MTS-1710 display.
VRR#
Voltage Ramp Rate
•
Sets the voltage ramp rate
•
For
Φ
-N and 2-
Φ
-N fault modes, specify values in volts/sec. Valid values are 0 -
2000.0 (volts/sec)
•
For
Φ
-
Φ
and 3-
Φ
fault modes, specify value in %/sec. This percentage is the
percentage of the nominal
Φ
-N voltage. Valid values are 0-1000.0 (%/sec).
•
A value of 0 turns off voltage ramping
•
In
Φ
-
Φ
fault modes, the %/sec ramp rate setting is only approximate.
VDU#
Voltage Duration
•
Set the voltage fault duration
•
Valid values are 0 - 99.999 (seconds)
•
A value of 0 turns off voltage fault duration.