RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-47
CU A002 15A
MANTA TEST SYSTEMS
6.7.2.1 INDIVIDUAL PHASE/AMPLITUDE SETTINGS MAP.
The following settings map shows the RS-232 commands associated with the MTS-1710 + slave current
unit when operating in the I3-WYE (true 3
Φ
) current mode:
6.7.2.2 INDIVIDUAL PHASE PROGRAMMING COMMANDS.
The PAM# command, described in Section 6.7.1.2, is the same for use with the MTS-1710 + MTS-1720
Two channel source. The PHS#,#,# command is extended to handle three-phase current, as follows:
Command
Description
PHS#,#,#
Individual Phase
•
Set individual phase value
•
First argument is the phase value. Valid values are -360.0 to 360.0
°
.
•
Second argument specifies the fault state. Valid values are 0 -2.
0 - prefault phase
1 - fault phase
2 - postfault phase
•
Third argument specifies the output. Valid values are 1 - 6.
MTS-1710 Settings Map (Individual Phase/Amplitude Mode)
Fault Type
FMD#
Operation mode
STT/DYN
Freq. reference mode
VFQ/LIN
Fault Phase
FMD#
Current mode
IMD5
Harmonic
VHM#/LHM#
Amplitude adjust mode
AAM1
Phase adjust mode
PAM1
Parameter
PREFAULT
FAULT
POSTFAULT
PRF#
POF#
Amplitude
Phase
Amplitude
Phase
Amplitude
Phase
VA
AVA#,0
PHS#,0,1
AVA#,1
PHS#,1,1
AVA#,2
PHS#,2,1
VB
AVB#,0
PHS#,0,2
AVB#,1
PHS#,1,2
AVB#,2
PHS#,2,2
VC
AVC#,0
PHS#,0,3
AVC#,1
PHS#,1,3
AVC#,2
PHS#,2,3
IA
AI1#,0
PHS#,0,4
AIA#,1
PHS#,1,4
AIA#,2
PHS#,2,4
IB
AIB#,0
PHS#,0,5
AIB#,1
PHS#,1,5
AIB#,2
PHS#,2,5
IC
AIC#,0
PHS#,0,6
AIC#,1
PHS#,1,6
AIC#,2
PHS#,2,6
Freq. [Hz]
FRQ#
FFI#
FPO#
Special Modes and Settings (via menu)
Timer Start Mode
IST/XST
Fault incidence angle
FIA#
Dynamic Meas. Mode
DMM#
Synchronizing mode
SYN0
Auto-reclose delay
TDR#