![Manta MTS-1700 SERIES Operation And Reference Manual Download Page 337](http://html1.mh-extra.com/html/manta/mts-1700-series/mts-1700-series_operation-and-reference-manual_1723616337.webp)
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL E-1
CU A002 15A
MANTA TEST SYSTEMS
APPENDIX E
MTS-1710 SYNCSCOPE PROGRAM
E.1 INTRODUCTION
Syncscope is a graphical demonstration aid for illustrating the MTS-1710’s synchronizing mode feature.
E.2 FEATURES
•
Pseudo real-time display of the Bus/Line and Bus/Generator voltage phasors against the
synchronizing element characteristic.
•
Pseudo real-time display of the voltage phasors at the time of breaker close (based on breaker advance
time).
•
Displays quantities as primary or secondary values.
•
Automatic setup for phase angle limit, voltage limit and frequency limit tests.
•
Display voltage limit characteristic based on the phasor voltage difference method or difference of
magnitudes method.
E.3 OPERATION
E.3.1 Setup
1. Connect the synchronizing device to the MTS-1710, as shown in Figure 3.15.
2. Connect the MTS-1710 COM1 port to your PC's RS-232 port with a standard serial cable. Turn on the
MTS-1710.
3. Start the program (SYNCSCOP.EXE) from the program icon, or from Windows [Start] menu.
4. When prompted, select the MTS-1710 as the equipment type.