RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-17
CU A002 15A
MANTA TEST SYSTEMS
FRR#
Frequency Ramp Rate
•
Sets the frequency ramp rate
•
Valid values are 0 - 10.0 (Hz/sec)
•
A value of 0 turns off frequency ramping
•
This command only takes effect in variable frequency reference mode.
FDU# Frequency
Duration
•
Set the frequency fault duration
•
Valid values are 0 - 99.999 (seconds)
•
A value of 0 turns off frequency fault duration
FFF#
Fault Final Frequency
•
Sets the fault final value for frequency ramping
•
Valid values are 40.000 - 80.000 (Hz)
•
This command only takes effect in variable frequency reference mode.
FPO#
Postfault Frequency
•
Sets the postfault frequency value
•
Valid values are 40.000 - 80.000 (Hz)
•
This command only takes effect in variable frequency reference mode.
LHM#
Line Harmonic
•
Sets the harmonic in line frequency reference mode
•
Valid values are 1 - 10
VHM# Variable
Frequency
Harmonic
•
Sets the harmonic in variable frequency reference mode (and in 25Hz frequency
reference mode)
•
Valid values are 1 - 10
FDF#
Frequency - Default
•
Sets the default variable frequency on power-up
•
Valid values are 40.000 - 80.000 (Hz)
•
This value will take effect the next time the MTS-1710 is turned on, or when
default settings are restored (see Section 5.8.1 for details).
F25
25Hz Frequency Mode
•
Sets 25Hz frequency reference mode
6.2.8.2 EXAMPLES.
Example 1 The following command sequence performs a frequency ramp from 60Hz to 58.219Hz at
0.3Hz per second.
Note that, if a stop trigger occurs, the output will change immediately to the postfault frequency value.
VFQ
<- select variable frequency reference mode
VHM1
<- select fundamental
DYN
<- dynamic operation mode for dynamic test