RS-232C INTERFACE - Section 6
MTS-1700 SERIES OPERATION AND REFERENCE MANUAL 6-23
CU A002 15A
MANTA TEST SYSTEMS
6.2.13 Fault Playback Commands
6.2.13.1 COMMANDS - 8 BIT DATA.
Command
Description
RCM#
Playback Mode
•
Valid values are 0 - 3
0 - playback off
1 - Internal data mode
2 - Internal data repetitive mode
3 - External data mode (requires Option -04)
•
This command also resets (clears) the fault playback data buffer.
RCR#
Playback Rate
•
Sets the fault playback rate. This should be set to be equal to the sample rate of
the rate of the fault waveform to be played back.
•
The anti-alias filter is automatically set to one half of the playback rate by this
command.
•
Valid values are 2.00 - 30.00 (kHz)
RCD#,#,#,#
Playback Data
•
This command specifies one set of data points for fault playback.
•
The arguments specify the value of Va, Vb, Vc and I respectively (In I1-LOW
and I3 current modes).
•
Valid values are 0 - 255 (binary offset code)
•
Each successive RCD command stores the next set of data points into the MTS-
1710’s fault playback data buffer. This data buffer is reset when an RCM#
command, or LOC command, is sent.
•
See Section 7.3.1 for details
•
When the MTS-1720 is connected, and the I3-WYE current mode is selected,
the RCD command takes six arguments, and is of the form RCD#,#,#,#,#,#
NOTE: See Section 7 for complete details on use of fault playback commands.
6.2.13.2 COMMANDS - 14 BIT DATA.
Command
Description
FPM#
Fault Playback Mode
•
Valid values are 0 - 3
0 - playback off
1 - Internal data mode
2 - Internal data repetitive mode
3 - External data mode (requires Option -04)
•
This command also resets (clears) the fault playback data buffer.
FPR#
Fault Playback Rate
•
Sets the fault playback rate. This should be set to be equal to the sample rate of
the rate of the fault waveform to be played back.