Service Manual
1-191
INSTALLATION
(1) The position of the drain pipe connection is shown in Figure 7.1.
(2) Prepare a polyvinyl chloride (PVC) pipe with 1-1/4 inch (32mm) outer diameter.
)DVWHQWKHWXEHWRWKHGUDLQKRVHZLWKWKHDGKHVLYHDJHQWDQGWKH¿HOGVXSSOLHGFODPS7KHGUDLQ
piping must be performed with a DOWN-SLOPE pitch of 1/25 to 1/100.
(4) Insulate the drain pipe after connecting the drain hose.
7.
'UDLQ3LSLQJ
Perform drain piping work and attach the insulations before refrigerant piping work.
Ɣ (QVXUHWKDWWKHGUDLQSLSHGLVFKDUJHVZDWHUSURSHUO\,IFRQQHFWHGLQFRUUHFWO\LWPD\FDXVHOHDNVOHDGLQJ
to property damage.
Ɣ 'RQRWSURYLGHDQXSZDUGVORSHRUDULVLQJSDUWIRUWKHGUDLQSLSH2WKHUZLVHWKHGUDLQZDWHUZLOOÀRZ
back into the unit and it may cause the water leakage when the unit operation is stopped.
Ɣ 'RQRWFRQQHFWWKHGUDLQSLSHZLWKDVDQLWDU\RUVHZDJHSLSHRUDQ\RWKHUGUDLQDJHSLSH
Ɣ :KHQWKHFRPPRQGUDLQSLSHLVFRQQHFWHGZLWKRWKHULQGRRUXQLWVWKHFRQQHFWHGSRVLWLRQRIHDFKLQGRRU
unit must be higher than the common pipe. The pipe size of the common drain pipe must be large
enough according to the unit size and number of units.
Ɣ $IWHUSHUIRUPLQJGUDLQSLSLQJZRUNDQGHOHFWULFDOZLULQJHQVXUHWRHQVXUHWKDWZDWHUÀRZVVPRRWKO\DVLQ
the following procedures.
'RQRWSXWWKHGUDLQSLSHIRUWKHLQGRRUXQLWLQWRWKHGUDLQDJHWUHQFKZKHUHFRUURVLYHJDVHVRFFXU
2WKHUZLVHSRLVRQRXVJDVHVÀRZLQWRWKHURRPZKLFKPD\FDXVHSRLVRQLQJ
NOTICE
9-1/4
14-31/32
31/32
2-9/32
2-9/32
31/32
31/32
7-13/32
1
1
-15/32
1-31/32 to
22-1
1/16 (Max.)
14-23/32 to 35-7/16 (Max.)
(Drain-Up Length)
Drain Piping (PVC Tube, VP25)
(Field-Supplied)
1/25 to 1/100 Down-Slope
Suspension Bracket
(Field-Supplied)
90
o
Elbow Pipe (VP25)
(Field-Supplied)
Lift Piping for Drain-Up
(PVC Tube, VP25)
(Field-Supplied)
Indoor Unit
Drain Pump
Drain
Pan
Rubber Boss
Drain Hose
(L: 11-13/16)
(Accessory)
Figure 7.1 Drain Piping
Common
Drain Piping
Connection
1/25 to 1/100 Down-Slope
Common Drain Piping
This drain pipe shall be
separating from other pipes.
Incorrect: Upward Slope
Unit
Rising Part
Incorrect
Correct
Indoor Unit
Auxiliary Drain Pan
(Field-Supplied)
To the Atmosphere
Figure 7.2 Auxiliary Drain Pan
NOTE:
When the relative humidity of inlet or ambient
DLUH[FHHGVDSSO\DQDX[LOLDU\GUDLQSDQ
¿HOGVXSSOLHGEHQHDWKWKHLQGRRUXQLWDV
shown in Figure 7.2.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...