Service Manual
2-15
OPERATION
NOTE
Ɣ 7KLVDLUFRQGLWLRQHUDGRSWVDKRWDLUFLUFXODWLRQV\VWHPIRUWKHKHDWLQJRSHUDWLRQ
If the space is large or the room temperature is excessively low, it takes time to heat the entire room.
,IWKHURRPKDVEHHQKHDWHGHQRXJKDQGGLVFKDUJHGDLUUHDFKHVDUHTXLUHGWHPSHUDWXUHWKHLQGLFDWLRQ
“HOT-START” will be turned OFF after heating the room.
Ɣ 7KHLQGLFDWLRQ
“HOT-START” may be displayed during, or right after, the defrosting operation.
“HOT-START” is activated during defrost to ensure comfort by reducing the delivery of cold air in the
heating cycle. This is NOT abnormal.
6. Automatic
Control
This air conditioner automatically starts the following operations according to the indoor conditions.
Three-Minute Guard
ƒ(QIRUFHG6WRSSDJH
The compressor remains off for at least three minutes once it has
stopped. If the system is started within approximately three minutes
DIWHULWKDVVWRSSHGWKH581LQGLFDWRULVDFWLYDWHG
However, the cooling operation or the heating operation remains off
and does not start until after three minutes has elapsed.
ƒ(QIRUFHG2SHUDWLRQ
If all indoor units of the system are Thermo-OFF within approximately
three minutes after the compressor has started, the compressor is
operated during three minutes continuously.
However, if all indoor units of the system are stopped by a controller,
compressor has stopped.
Cooling
and
Dry
Frost Prevention
When the indoor unit is operated at a low discharge air temperature,
the cooling operation may be changed to fan operation for a while to
avoid frost formation on the indoor heat exchanger.
Self-Cleaning of
Expansion Valve
The expansion valve self-cleaning when the cooling operation has
VWRSSHG7KHVRXQGRIZKLFKWKHUHIULJHUDQWÀRZVPD\EHKHDUGIURP
the indoor unit during the self-cleaning. This is not abnormal.
Heating
Hot Start
To prevent cold air discharge in the room, the fan speed is controlled
from the slow position and the low position and then to the set position
according to the discharge air temperature.
$WWKLVWLPHWKHORXYHULV¿[HGKRUL]RQWDOO\DQG³+2767$57´LV
displayed on the LCD of the wired controller.
Defrost Operation
The indoor unit fan operation is stopped to prevent cold air discharge
during the defrost operation. At this time, the indication “HOT-START”
is displayed on the LCD of the wired controller and the indoor unit fan
ORXYHUDQJOHLV¿[HGKRUL]RQWDOO\
Residual
Heat Removal
When the heating operation is stopped, the indoor fan operation may
be kept at the slow position for a maximum of two minutes to lower
temperature of the inside of the indoor unit.
Prevention
of Overload
Operation
When the outdoor temperature is high (approx. 70
o
F (21
o
C) or more)
during the heating operation, the operation is stopped by activation of
the outdoor thermistor.
7KHV\VWHPLVHTXLSSHGZLWKWKHIROORZLQJIXQFWLRQV
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...