4.4 Piping Work
(2) When cutting piping, secure the adequate depth for brazing as shown in the following table.
(1) Use clean copper pipes without any moisture or foreign materials on inner surface of pipes. When
connecting refrigerant pipe, cut the copper pipes with a pipe cutter as shown below. Also blow-out the
pipes with nitrogen or compressed air to ensure that no dust remains inside the pipe. Do NOT use a saw, a
grindstone or others which causes a large amount of cutting powder.
Pipe Cutter
Pipe
Connection
Part
Deburring
B
A
4.3 Connection Procedure for Piping Joint
When connecting liquid piping for a unit with a capacity of 15 MBH or smaller, and with a length of piping 49.2ft (15m)
RUORQJHUDSSO\DSLSLQJVL]HRILQFKPP6HFXUHWKHFRQQHFWLQJSLSHDVVKRZQLQWKH¿JXUHEHORZ8VH
the insulation attached to the indoor unit.
Brazing
Insulation Attached to Indoor Unit
Field-Supplied Refrigerant Piping
Field-Supplied Insulation
Fix this part with the attached cord
band or field-supplied vinyl tape.
Insulate this part with the
attached insulation.
Use the flare nut of the indoor unit.
Expander for Liquid Line (Accessory)
Flare the pipe after inserting the flare nut.
Indoor
Unit
Ɣ&DXWLRQIRU5HIULJHUDQW3LSLQJ
Hole
Rain water
can enter.
When installing pipe through the
wall, install an end cap at the end of
the pipe.
Attach an end cap
or vinyl tape.
INCORRECT
CORRECT
INCORRECT
CORRECT
Do NOT lay the pipe directly
on the ground.
Attach an end
cap or vinyl tape.
INCORRECT
CORRECT
Attach an end cap
or vinyl tape with a
rubber band.
inch (mm)
Diameter
(A)
Min. Insertion Depth
(B)
3/16 < A < 5/16
1/4 (6)
(5 < A < 8)
5/16 < A < 15/32
9/32 (7)
(8 < A < 12)
15/32 < A < 5/8
5/16 (8)
(12 < A < 16)
5/8 < A < 31/32
13/32 (10)
(16 < A < 25)
31/32 < A < 1-3/8
15/32 (12)
(25 < A < 35)
1-3/8 < A < 1-25/32
9/16 (14)
(35 < A < 45)
6HUYLFH0DQXDO
INSTALLATION
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...