Service Manual
3-71
TROUBLESHOOTING
Alarm
Code
Abnormality of Thermistor for Indoor Unit Inlet Air Temperature
(Inlet Air Thermistor)
NOTE:
7KLV¿JXUHLVDSSOLFDEOHWRWKHIROORZLQJWKHUPLVWRUV
1. Inlet Air Thermistor (THM1), 2. Liquid Pipe Thermistor (Freeze Protection) (THM3), 3. Gas Pipe Thermistor (THM5),
4. Outlet Air Thermistor (THM2), 5. Outside Air Thermistor or Remote Thermistor (THM4)
O
7KH581LQGLFDWRUUHGÀDVKHV
O
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code*
1)
,
the model name*
1)
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
*1) Except for some models.
+
7KLVDODUPFRGHLVGLVSOD\HGZKHQDVKRUWFLUFXLWNȍRUOHVVRUGLVFRQQHFWLRQNȍRUPRUHRI
the thermistor is detected during a heating or cooling operation. The operation automatically restarts
when the malfunction is removed.
Yes
Yes
Connect them.
No
Failure of
Thermistor
Failure of I.U. PCB
No
Is thermistor THM1
(for inlet air temp.)
connected to THM1
of I.U. PCB?
Is resistance of THM1
between 0.24k
Ω
and
840k
Ω
?
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Failure of
Inlet Air
Thermistor
Check resistance.
Replace thermistor
if faulty.
Failure
Check connection.
Correctly connect wires.
Incorrect Connection
Replace I.U. PCB
and check operation.
Replace I.U. PCB
if faulty.
Failure of I.U. PCB
0
10
20
30
40
50
60
70
80
(-15) (-10) (-5) (0)
(5) (10) (15) (20) (25) (30) (35) (40) (45) (50) (55) (60)
82
61
46
35
27
20.5
16
12.5
10
8
5.3
3.6
2.5
90
Thermistor
Resistance
(kΩ)
5
14
23
32
41
50
59
68
77
86
95 104 113 122 131 140
Ambient Temperature (
o
F(
o
C))
Indication on Outdoor Unit PCB
(Alarm Code 11 ~ 19)
Unit No. of
Malfunctioning Indoor Unit
Alarm Code
(11 ~ 19)
Example of 4-way Cassette Type
Inlet Air Thermistor
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...