(Cleaning Indoor Unit Heat Exchanger)
MAINTENANCE
4-148
Service Manual
3ODFHDSSUR[LPDWHO\WKUHHJDOORQVOLWHUVRIQHXWUDOFOHDQLQJDJHQWIRUDOXPLQXP¿QVLQDVXSSO\
tank.
(8) Insert the spray nozzle through the hole of the cleaning water collector. Operate the water pump and
clean the heat exchanger. After cleaning, spray clean water to remove the cleaning water. Adjust the
SUHVVXUHRIWKHZDWHUSXPSVRWKH¿QVDUHQRWGDPDJHG
NOTES:
,IWKHFOHDQLQJZDWHUUHPDLQVRQWKH¿QVWKH\ZLOOEHFRUURGHG
2. Adjust the pressure of the pump at 36 to 71 psi (2.5 to 5.0 kg/cm
2
VRWKH¿QVDUHQRWGDPDJHG
Tool
Clean Water, Neutral Cleaning Agent,
Water Pump, Cleaning Spray
TURN OFF all power source switches.
Cleaning
Spray
Bucket
Cleaning Agent for
Aluminum Fins