Service Manual
1-273
INSTALLATION
(4) Capacity Code Setting (DSW3)
No setting is required, due to setting before shipment. This switch is utilized for setting the capacity
code which corresponds to the capacity of the indoor unit.
1 2 3 4
ON
OFF
Setting Position
06
08
12
Indoor Unit Capacity
(MBH)
15
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
(5) Unit Model Code Setting (DSW4)
No setting is required. It is for setting the model code of the indoor unit.
8.6 DIP Switch Settings
(1) Turn OFF the power supply to both indoor and outdoor units before adjusting DIP switch settings.
Otherwise, the settings will be invalidated and not take effect.
3RVLWLRQVRI',36ZLWFKHVRQWKH3&%DUHVKRZQLQWKH¿JXUHEHORZ
DSW4
(Unit Model Code Setting)
DSW9
(Optional Function Setting)
DSW7
(Fuse Recovery)
DSW3
(Capacity Code No. Setting)
RSW2, DSW5
(Refrigerant Cycle No. Setting)
RSW1, DSW6
(Indoor Unit No. Setting)
Indoor Unit PCB
DSW4
DSW9
DSW7
DSW5
DSW6
RSW2
RSW1
DSW3
(3) Unit No. Setting
Setting is not required.
Indoor unit numbers are set by the auto-address
function. If an indoor unit number setting is
required, set the unit number of all indoor units
respectively and sequentially by following setting
position. It is recommended that you assign a
number to each indoor unit from “1”. A maximum
of 64 indoor units per refrigerant cycle can be
connected to an H-LINK ll System. Though the
available numbers range from zero to 63, the
applicable number for the 64th indoor unit in
theory supplants the number "zero".
For the centralized control, this setting is
required.
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW6 (Tens Digit)
Unit No. Setting
RSW1 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.16 Unit
DSW6
RSW1
Set No.1 Pin at ON side
Set at "6"
3
4
1
0
8
9
2
56
7
3
4
1
0
8
9
2
56
7
Before shipment, DSW6 and RSW1 are set at "0".
For the units supporting H-LINK II,
the unit No. can be set for Max. 64 indoor units
(No.0~63).
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...