Service Manual
OPERATION
8.4 Adjust Setting Temperature Range of Local Wired Controller
1. Select “Setting temp. range of the
remote control” from the “Menu”
screen.
2. Select a target to set a temperature
range (All Groups/Block/Group).
Ɣ
Blue buttons represent Groups
with temperature range settings.
Ɣ
White buttons represent groups
where temperature range
settings are not available.
Ɣ
Wireless receiver kits with
model numbers: C4IRK01,
C2IRK01, C1IEK01, and
CWDIRK01 should not be used
to set up Groups in the Central
Controller.
A temperature
setpoint outside the range
can be set from a wireless
controller.
NOTE:
The following Group cannot be
selected:
Ɣ
Without a wired controller
Ɣ
The representative wired
controller Group is not the
standard unit supporting H-LINK
II
(temperature setpoint range
is from 66 to 86°F for COOL,
and from 62 to 86°F for
HEAT).
3. Touch
“ ” or “ ”
to set a minimum
cooling temperature or maximum
heating temperature.
4. Touch “Back” when setting other
group temperature ranges, to
return to the selection screen.
3. Touch “Done” to return to “Monitor
1 (All Groups)” or “Monitor 2
(Block)”.
2
1
3
4
5
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...