(17-23/32 x 17-23/32)
(11-13/16 x 11-13/16)
Min. A
Min. A
Min. 2-3/4
Min. 2-3/4
Electrical Box
Service Access
Door
Service Space
2-Suspension Bolt
(Field-Supplied)
Upper Side
Bottom Side
M10 or W3/8
Unit: inch
Service Manual
1-97
INSTALLATION
4.2 Initial
Check
Ɣ ,QVWDOOWKH&KDQJH2YHU%R[ZLWKDSURSHU
clearance around it for maintenance working
space, as shown in Fig. 4.1 below.
Size
Model
A
COBS048B21S
11-13/16
COBS096B21S
15-3/4
Fig. 4.1 Maintenance Space
Ɣ &KHFNWRHQVXUHWKDWWKHFHLOLQJLVVXI¿FLHQWO\
strong to sustain the Change-Over Box. If the
ceiling is weak, abnormal sound and vibration
may occur.
Ɣ $FKDQJHLQWKHW\SLFDOUHIULJHUDQWÀRZVRXQGV
may be heard or perceived from the Change-
Over Box when the electric expansion valve in
the Change-Over Box is activated. Therefore,
take the following action to minimize the sound.
(A) Install the Change-Over Box inside the
ceiling. As for the ceiling material, select a
material like a plasterboard at least 1 inch
(9mm), which minimizes operation sound.
(B) Do not install the Change-Over Box in a
place near bedrooms or hospital rooms.
Ɣ $FKDQJHLQWKHW\SLFDOUHIULJHUDQWÀRZVRXQGV
may be heard or perceived from the Change-
Over Box when the operation is changed to
cooling/heating mode.
Therefore, install the Change-Over Box in the
ceiling of the corridor so that the refrigerant
ÀRZLQJVRXQGPD\QRWEHKHDUGLQWKHURRP
Ɣ 'RQRWLQVWDOOWKH&KDQJH2YHU%R[LQDKRW
or humid place, such as a kitchen, to prevent
condensation on the outer surface of the
Change-Over Box.
When installing the Change-Over Box in such
places, apply additional insulation.
Ɣ 3D\DWWHQWLRQWRWKHIROORZLQJSRLQWVZKHQWKH
Change-Over Box is installed in a hospital or
other facility where there are electronic waves
from medical equipment.
(A) Do not install the Change-Over Box where
the electromagnetic wave is directly radiated
to the electrical box or intermediate wiring
(transmission wiring).
(B) Install the Change-Over Box and
components as far as practical or at least
10 ft (3m) from the electromagnetic wave
radiator.
& ,QVWDOODQRLVH¿OWHUZKHQWKHSRZHUVXSSO\
emits harmful noises.
Ɣ 7KHLQVWDOODWLRQSODFHVKRXOGEHFRQYHQLHQW
for the refrigerant piping or electrical wiring
connection.
Ɣ 'RQRWGULOORUGULYHVFUHZVLQWRWKHFDELQHW
Use only mounting points provided.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...