1-648
Service Manual
INSTALLATION
No.
Condition
Items to be Checked
Action
1
The management software
doesn’t exit when the UPS
requests the computer to
shutdown.
Is the management software
NOT set to quit the current
session of Windows?
Change the settings for the management
software to exit the current Windows session
as shown below:
(a) Exit the management software.
(b) Open manager_info.ini in the
[/centralstation/manager] folder.
(c) Change:
[ForceCloseOnWindowsSessionEnd=0] to
[ForceCloseOnWindowsSessionEnd=1] in
[Others] section.
(d) Overwrite, save and close manager_info.ini.
(e) Restart the management software.
(f) Check that the management software
exits correctly when the UPS requests
the computer to shutdown.
2
[No response] indicated on the
management software title bar.
Is the process lengthy
and time consuming in its
execution?
If the process becomes overly time
consuming, the message “No Response”
will display. This is normal. Be patient and
do not attempt to back out of the command.
When “No Response” disappears, the
process is concluded.
Miscellaneous
Modi
¿
cation from Non RC equipped to RC equipped units.
In any of the following procedures, cancel recognition of “Non RC equipped” and the remote control (Central
Control display).
The nature of this procedure is complex. Proceed by
¿
rst selecting on the check box next to the number.
<When the emergency stop is available>
Ƒ
(1) Repeat the connection veri
¿
cation procedure for this H-LINK in [Settings] > [Unit Register].
Ƒ
(2) Display each unit status in [Monitor], and verify that icons (representing non RC equipped units) are not
shown.
Ƒ
(3) Activate the emergency stop command to exceed one minute elapsed time and then cancel out of it.
Ƒ
(4) Verify that the [Central control] setting for the RC is canceled. (Verify for all indoor units of this H-LINK.)
NOTE:
Indoor Units:
When performing control function selections, repeat again after canceling settings for emer-
gency stop. The control status will display: “Stop”, FAN, 82°F (28°C), LOW (fan speed) and (1), (Louver).
Assume control again if necessary.
<When the emergency stop is not available>
Ƒ
(1) Copy Connection_Ininfo_##.dat, Connection_Block.dat, and Connection_Group.dat in [/centralstation/rcv/
H-LINK**/mnt/ram/harcweb1/download] folder to C drive.
NOTE:
1. “**” of “H-LINK**” is H-LINK No.(00-15) (that is indicated in the RC central control display).
2. “##” of Connection_Ininfo_##.dat is 01-64 is in the folder.
Ƒ
(2) Copy webcon**_data.csv in [/centralstation/manager/data] to the C drive.
NOTE:
“**” of Webcon** is H-LINK No.(00~15) (that is indicated in the RC central control display).
Ƒ
(3) Copy Unit_restore.bat and BlockGroup_restore.bat (that are found on the installation CD). Copy to C:
Drive.
Ƒ
(4) After three minute’s time, remove the wire from the adapter to the H-LINK.
Ƒ
(5) Verify that displayed values (in Central Control) have vanished from the RC panel screen. Verify for all
indoor units in this H-LINK.
Ƒ
(6) Click on [Connection check] in [Settings] > [Unit register] in the management software.
Ƒ
(7) Select [No] on the [Utilize registered data?] pop-up message.
Ƒ
(8) Select [Yes] in the [Deleting the registered data to start checking connection.] pop-up message.
Ƒ
(9) Connect the wire from H-LINK after 10 seconds.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...