Service Manual
5-21
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
NOTE:
Reduction rates are approximate, these may change slightly depending on the outdoor unit model.
(2) Night Shift (Low Noise) (Function Setting “ni”)
Press “PSW3” and select the setting condition “1” or “2” for the Night Shift (Low Noise) “
”. Then, this
function can be set. “ni”=1 reduces the upper limit of the outdoor fan rotation and the compressor frequency
as shown below in any operation. “ni”=2 is adapted only for cooling operation. In heating operation, “ni”=2
is same as “ni”=0.
The Night Shift operation should be used if the capacity has the margin to be allowed for the capacity
decrease and the low sound operation is required especially in the nighttime.
< Night Shift >
at Heating Operation
Reduction Rate of Upper Limit
Outdoor Fan Radiation
= 75%
at Cooling Operation
Reduction Rate
of Upper Limit
Outdoor Fan
Radiation
72 (22)
77 (25)
65%
75%
90%
86 (30)
92 (33)
Outdoor Temperature [
o
F (
o
C)]
Reduction Rate of Maximum
Outdoor Fan Rotation
Compressor Frequency
“ ni ” Setting
Condition
Operation
Cooling
(Including Dry Operation)
Except for
Cooling
Cooling
(Including Dry Operation)
Except for
Cooling
0
No Effect
(Default Setting)
Not Changed
(=100%)
Not Changed
(=100%)
Not Changed
(=100%)
Not Changed
(=100%)
1
Night Shift1
Shown as below
Shown as below
60%
60%
2
Night Shift2
(only for Cooling)
Shown as below
Not Changed
60%
Not Changed
at Heat Recovery Operation
86 (30)
92 (33)
75%
90%
Outdoor Temperature [
o
F (
o
C)]
Reduction Rate
of Upper Limit
Outdoor Fan
Radiation
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...