Service Manual
1-367
INSTALLATION
Ɣ
Table A: Optional Setting Items for Function Selection
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
Setting
1
b1
Cancellation of Heating
Temperature Compensation
due to Uneven Heat Load
ż
00
01
02
03
04
Standard (Set Temp. +7
o
F (+4
o
C))
Removal
Set Temp. +3
o
F (+2
o
C) (*1)
Set Temp. +5
o
F (+3
o
C)
Set Temp. +2
o
F (+1
o
C)
2
b2
Circulator Function at
Heating Thermo-OFF
ż
00
01
Not Available
Available
3
b3
Enforced 3 Minutes
Minimum Operation Time of Compressor
ż
00
01
Not Available
Available
4
b4
Change of Filter Cleaning Time
ż
00
01
02
03
04
Standard
100 hrs
1,200 hrs
2,500 hrs
No Indication
5
b5
Selecting the Operation Mode
×
00
01
Standard
Fixed
6
b6
Selecting the Temperature Setpoint
×
00
01
Standard
Fixed
7
b7
Designated Operation Cooling Unit
×
00
01
Standard
Fixed
8
b8
Automatic COOL/HEAT Operation
×
00
01
Not Available
Available
9
b9
Selecting the Fan Speed
×
00
01
Standard
Fixed
10
bA
Not Prepared
-
-
Not Used
11
bb
Cooling Temperature Compensation
due to Uneven Heat Load
×
00
01
02
Standard (No Compensation)
Set Temp. –2
o
F (–1
o
C)
Set Temp. –3
o
F (–2
o
C)
12
bC
Not Prepared
-
-
Not Used (Use as 00 conditions)
13
bd
Not Prepared
-
-
Not Used (Use as 00 conditions)
14
bE
Not Prepared
-
-
Not Used (Use as 00 conditions)
15
C1
Not Prepared
-
-
Not Used (Use as 00 conditions)
16
C2
Not Prepared
-
-
Not Used
17
C3
Not Prepared
-
-
Not Used
18
C4
Not Prepared
-
-
Not Used
19
C5
High-Speed
(Except for Hi-Speed at Heating Thermo-OFF)
ż
00
01
02
Not Available
Hi Speed 1
(*2)
Hi Speed 2
20
C6
High-Speed at Heating Thermo-OFF
ż
00
01
Not Available
Available
21
C7
Canceling of Enforced 3 Minutes
Minimum Operation Time of Compressor
ż
00
01
Standard
Cancellation
22
C8
Thermistor for the Controller
ż
00
01
02
(*3)
23
C9
Not Prepared
-
-
Not Used
24
CA
Not Prepared
-
-
Not Used
25
Cb
Reason for Forced Stoppage
×
00
01
Forced Stoppage Input: A Contact
Forced Stoppage Input: B Contact
26
CC
Not Prepared
-
-
Not Used (Use as 00 conditions)
27
Cd
Not Prepared
-
-
Not Used (Use as 00 conditions)
28
CE
Not Prepared
-
-
Not Used (Use as 00 conditions)
29
CF
Change of Louver Swing Angle
ż
00
01
02
Standard (7-Step Operation)
Cold Draft Prevention
(5 Steps: lower 2 steps cut off)
High Ceiling
(5 Steps: upper 2 steps cut off)
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...