3-132
Service Manual
TROUBLESHOOTING
Abnormalities of Devices
Other
Abnormalities
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Cooling or
Heating
Operation
with
Abnormal
Sound
Outdoor Fan
does Not Operate
even when
Compressor
is Operating
Is there any abnormal
sound from Inside of
compressor?
Replace compressor.
Wear or
Breakage of
Internal
Comp. Parts
Check expansion valve
opening.
Check each part is
tightly fixed.
Abnormal
Sound from
Compressor
Failure of
Installation
Tightly fix it.
Ensure superheat.
Liquid Ref.
Compression
Check resistance of
crankcase heater or fuse.
Replace crankcase
heater or fuse.
Crankcase
Heater does
Not Get Warm
Check it by viewing.
Remove foreign
particles.
Foreign Particles Inside
Fan Casing
Check it by viewing.
Adjust position of
fan wheel.
Indoor Unit Fan Wheel
Contacts Casing
Check it by viewing.
Adjust position of
propeller fan.
Outdoor Unit Propeller Fan
Comes in Contact with Fan Shroud
Check surface of
contacts.
Replace magnetic
switch.
Humming Sound from
Magnetic Contactor
Check each fixing
screws.
Tightly fix it.
Abnormal Vibration of
Cabinets
Check obstacles.
Remove obstacles.
Obstacle at Outdoor Fan
Check wiring.
Correctly connect wires.
Disconnected Wire for
Indoor Fan
Check AC chopper.
Replace AC chopper.
Failure of AC chopper
Wait for switching of
reversing Valve.
(1 to 3 minutes)
If the reversing valve is
not switched, check for
insufficient refrigerant.
Preparatory State for
Heating Operation
Indoor Fan
does Not Operate
even when
Compressor
is Operating
Check operation
pressure.
Add refrigerant.
Discharge pressure does
not increase higher than
2.2MPa due to insufficient
refrigerant.
Check each part is
tightly secured.
Check each
tightening screws.
Discharge pressure does
not increase higher than
319 psi (2.2MPa) due to
LQVXI¿FLHQWUHIULJHUDQW
Is there any abnormal
sound from inside of
compressor?
Tightly secure it.
Tightly secure it.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...