Service Manual
1-219
INSTALLATION
5. Mounting the Indoor Unit
x
Hoist the indoor unit but do not apply any force against the drain pan (the air outlet portions and the
GUDLQSDQSRUWLRQ,IWKHUHLVLQVXI¿FLHQWDFFHVVIRUDKRLVWWKHZRUNPXVWEHSHUIRUPHGPDQXDOO\E\
two skilled installers.
x
Suspend the unit by handling the suspension
brackets at all four corners of the unit. Do not
apply any pressure onto the polystyrene drain
pan or pan outlets during the installation process.
x
Insert the suspension bolts into the notches of
the suspension brackets to capture the unit.
Secure the unit using nuts and washers. Then
check that the washers serve as stoppers at the
rising parts of the suspension brackets.
NOTE:
$IWHUVHFXULQJWKHXQLWSLSLQJDQGHOHFWULFSRZHU
needs to be installed inside the ceiling area
adjacent to the unit. If a false ceiling is already in
SODFHGHWHUPLQHWKHSURSHUSDWKZD\IRUSLSLQJ
and electrical lines before the unit is installed.
6. Spacial adjustments to accommodate the unit into a false ceiling:
x
$GMXVWWKHSRVLWLRQRIWKHXQLWDVVKRZQDWULJKW
and maintain the mounting position of the unit
in accordance with Items 2. and 3. on the previous pages
within
+3/16
0
inch (
+5
0
mm).
x
The pattern board (template) for the installation and
the checking scale are printed on the packing.
Cut off the checking scale for dimension of opening from
packing to adjust the position of the indoor unit.
Indoor Unit
(Viewed from Bottom Side)
Surface of Flange
13/32
to 1-3/8
13/32
to 1-3/8
13/32
to 1-3/
8
13/32
to 1-3/8
Unit: inch
a. False-ceiling applications: Detach the
printed scale from the pattern board
(template). Raise the unit into position
and use this scale for clearance
adjustments between the unit and the
edge of the opening.
b. False-ceiling applications (without
opening): Use the outer edge of the
pattern board (template) to cut an
opening in the false ceiling. Raise the
unit into position and use this scale to
make minute clearance adjustments
as described in Item a.
Pattern Board (Template)
Dimension for Opening
Dimension for Opening
c. Incomplete false-ceiling applications
(panels not in place): Secure the
pattern board (template) to the unit
with the four M6 screws provided and
raise as shown into position. Make
minute clearance adjustments as
ceiling panels are installed.
Pattern Board
(Template)
Dimension for
Opening
Dimension for
Opening
Suspension Bolt
Indoor Unit
Screw (M6)
Ceiling Surface
Pattern Board
(Template)
Indoor Unit
Ceiling
Surface
Checking
Scale for
Dimension
Opening
Check the dimension of
opening within
Max. 1- 3/8 inch (35mm)
Min. 13/32 inch (10mm)
at each side.
Indoor Unit
Checking
Scale for
Dimension
Opening
Adjust this
portion of
the checking
scale to the
ceiling surface.
Adjust this portion
of the checking
scale to the unit
bottom surface.
Suspension Bolts
Suspension
Bracket
Drain Pan
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...