Service Manual
1-369
INSTALLATION
No.
Items
Optional Function
Individual
Setting
Setting
Condition
Contents
Setting
55
F3
Automatic Reset of Setting Temperature
(*5)
×
00
01
Not Available
Available
56
F4
Automatic Reset Time
×
00
01
02
03
30 min.
15 min.
60 min.
90 min.
57
F5
Automatic Reset Temperature
for Cooling (*6)
×
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
58
F6
Automatic Reset Temperature
for Heating (*7)
×
62 (17)
64 (18)
66 (19)
68 (20)
70 (21)
72 (22)
74 (23)
76 (24)
77 (25)
78 (26)
80 (27)
82 (28)
84 (29)
86 (30)
62
o
F (17
o
C)
64
o
F (18
o
C)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
59
F7
Operation Stoppage Prevention by
Controller Operational Error (*8)
×
00
01
Not Available
Available
60
F8
Lock Function for Operation Mode
Selection
×
00
01
Not Available
Available (Factory-Setting)
61
F9
Lock Function for Temperature Setting
×
00
01
Not Available
Available (Factory-Setting)
62
FA
Lock Function for Fan Speed Selection
×
00
01
Not Available
Available (Factory-Setting)
63
Fb
Lock Function for Swing Louver Operation
×
00
01
Not Available
Available (Factory-Setting)
64
FC
Cooling Lower Limit for Setting
Temperature (*6)
×
00
01
02
03
04
05
06
07
08
09
10
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
65
Fd
Heating Upper Limit for Setting
Temperature (*7)
×
00
01
02
03
04
05
06
07
08
09
10
11
12
64
o
F (18
o
C)
66
o
F (19
o
C)
68
o
F (20
o
C)
70
o
F (21
o
C)
72
o
F (22
o
C)
74
o
F (23
o
C)
76
o
F (24
o
C)
77
o
F (25
o
C)
78
o
F (26
o
C)
80
o
F (27
o
C)
82
o
F (28
o
C)
84
o
F (29
o
C)
86
o
F (30
o
C)
66
FE
Not Prepared
-
-
Not Used (Use as 00 conditions)
67
FF
Not Prepared
-
-
Not Used (Use as 00 conditions)
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...