1-54
Service Manual
INSTALLATION
B
First Branch
Outdoor Unit Capacity
(MBH)
Model
72 - 120
MW-NP452X2
144
MW-NP692X2
168 - 360
MW-NP902X2
C
for
Three Pipes Portion
Total
Indoor Unit Capacity
(MBH)
No. of Header
Branches
Model
36 - 72
8
MH-NP288X
D
for
Two Pipes Portion
Total
Indoor Unit Capacity
(MBH)
No. of Header
Branches
Model
36 - 60
4
MH-NP224A
36 - 72
8
MH-NP288A
< Line Branch >
< Header Branch >
C
Line Branch after First Branch (Three Pipes Portion)
Total
Indoor Unit Capacity
(MBH)
Model
< 41
MW-NP142X2
42 - 86
MW-NP282X2
87 - 113
MW-NP452X2
114 - 155
MW-NP562X2
156 - 185
MW-NP692X2
> 186
MW-NP902X2
NOTE:
If
C
“Line Branch after First Branch” is larger than
B
“First Branch”, use the same model as
B
“First Branch”.
D
Multi-Kit after First Branch (Two Pipes Portion)
Total
Indoor Unit Capacity
(MBH)
Model
< 86
MW-NP282A2
87 - 125
MW-NP452A2
126 - 185
MW-NP692A2
> 186
MW-NP902A2
Multi-Kit (Optional Parts)
5HIHUWRWKH¿JXUHRQWKHSUHYLRXVSDJH
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...