Service Manual
3-61
TROUBLESHOOTING
*1): When replacing or checking for the inverter part, make sure to perform the electric discharge work according to
Section 4.3.1.1 “High Voltage Discharge Work for Replacing Parts”.
*2): When replacing or checking for the fan controller, make sure to perform the electric discharge work according to
Section 4.3.1.1 “High Voltage Discharge Work for Replacing Parts”.
*3): When the fuse for the fan controller is blown, the fan controller may be broken too.
In this instance, the fan controller should be replaced.
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Check conduction.
Check for loose
screw connections.
Replace or repair
wires, or tighten screws.
Check connection Nos.
Correctly connect wires.
Check connection.
Repair wiring
connection.
Replace PCB if faulty.
Replace power fuse,
power transistor, and
diode module.
Replace incoming
current limit resistance.
Between O.U. PCB,
Inverter PCB and
Fan Controller
Disconnected
Wires,
Contact Failure or
Incorrect
Connection
Check continuity of
wires.
Check for loose
screw connections.
Check connection No.
Replace or repair
wires, tighten screws
or correct wires.
Power Source Wiring
for Outdoor Unit
Disconnected Wires
to PCB
Faulty PCB
Blown Power Fuse
Disconnected
Incoming Current Limit
Resistance
Check conduction of
power fuse, power
transistor, diode module.
Check resistance of
incoming current limit
resistance.
Disconnected Wires,
Contact Failure
Incorrect Wiring
Incorrect Wiring
Failure of
O.U. PCB,
Inverter PCB and
Fan Controller
Failure of
Electrical
Components
Power Fuse,
Resistance
Blown Fuse
(Fan Controller)
Check conduction
of fuse.
Replace Fan Controller
if faulty *3)
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...