Service Manual
INSTALLATION
< Check of the Motion Sensor >
3HUIRUPWKHPRWLRQGHWHFWLRQZDYLQJDKDQGHWFXQGHUWKHPRWLRQVHQVRURIWKHVHOHFWHG
indoor unit for approximately 10 to 15 seconds.
&KHFNWKHYDOXHRI³T´aTDIWHU
(*1)
seconds from starting the motion detection at Item 1.
The detection information from the motion sensor against the motion detection is displayed a
range of 0% to 100%.
(*1): The communication cable between the indoor unit and the wired controller is on a 30 second cycle.
Timing for motion detection and the detected information display is shown below.
< Check of the Radiation Sensor >
1. Check the value for
“q2”
. If that value differs greatly from the air temperature at the installation
ORFDWLRQDIDLOXUHRIWKHUDGLDWLRQVHQVRUPD\RFFXU7KHUDGLDWLRQVHQVRUZLOOLQGLFDWHUHDGLQJV
from (-22 to 140
o
F (-30 to +60
o
C)).
2. Press “Back/Help” and return to the display.
3. Check that the value of
“q3” ~ "q6"
is neither 0% nor 100%.
,IWKHYDOXHGLVSOD\HGLVRUUHSHDWWKHSURFHGXUHIURP,WHP,IWKHVDPHYDOXH
UHDSSHDUVLWPD\EHDPDOIXQFWLRQRIWKHPRWLRQVHQVRU
NOTE:
Refer to the operator's manual for indoor
XQLWVHWWLQJVVHWXSRIWKHPRWLRQVHQVRU
³0RWLRQ6HQVRU6HWWLQJ´
“If Absent” and “Check Interval” can be set.)
30 sec.
Motion Detection
Detected Information
Display
(for 30 seconds)
: Communication Data
Cycle 30 seconds.
30 sec.
H 7KRXJKWHPSHUDWXUHUHFRUGLQJVE\WKHWKHUPLVWRUVDUHLQYDOLGGXULQJWKH7HVW5XQSKDVHWKH
protection devices are valid.
f. For VRF System
$FFRUGLQJWRWKHODEHO³&KHFNLQJ0HWKRGE\6HJPHQW'LVSOD\´DI¿[HGWRWKHLQVLGHRIWKHIURQW
FRYHURIWKHRXWGRRUXQLWFKHFNWHPSHUDWXUHSUHVVXUHDQGRSHUDWLRQIUHTXHQF\DQGLQWHUFRQQHFWHG
indoor unit numbers by 7-Segment displays.
J 7RFRPSOHWH7HVW5XQSUHVV³
On/Off” again or wait for the
set Test Run time to pass.
:KHQFKDQJLQJWKH7HVW5XQWLPHSUHVV³
” or “ ” to select
“Test Time”
7KHQVHWWKHWHVWUXQWLPHWRPLQXWHV
by pressing “ ” or “ ”.
Adj.
Sel.
OFF
Test Run: 2 units
MODE
SPEED
AUTO
COOL
LOUV.
Test Time
120min
Inverter
60Hz
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...