1-336
Service Manual
INSTALLATION
6. Pull down the two "U" shaped hooks found on
the indoor unit.
7. Remove the corner pocket covers and
temporarily mount the decorative panel in
place. Fit the corner position for the refrigerant
pipe connection at the indoor unit with the
position stamped as
“Ref. Pipe
”
.
Then, fasten the C-shaped hinges to the
U-shaped hooks (two portions).
$I¿[WKHGHFRUDWLYHSDQHOWRWKHPRXQWLQJSODWH
with the factory-supplied long screws (M6 cross
screws).
NOTE:
Before mounting the decorative panel, remove
the corner pocket covers. Holes for long screws
are located in the corner pockets.
5. Verify that the distance between the under surface of the indoor unit and the under surface of the false
ceiling is 15/32 inch (+3/16 inch) or 12 mm (+ 5.0 mm) (*1) as shown below. Tighten the long screws until
they make contact with the stopper on the mounting plate. Verify that the distance between the under
surface of the mounting plate and the under surface of the corner panel is 1-1/32 inch (26mm) (*2) as
shown.
The long screws are tightened to seal against moisture incursion and that no gap should exist between
the false ceiling surface and the indoor unit. However, during tightening the panel may be slightly
deformed. This is considered normal.
Electrical Box
Refrigerant Pipe
Connections
Indoor Unit
C-Shaped Hinges
Mounting
Plate
Decorative
Panel
Long Screws
(Q’ty 4)
Stamp
“Ref. Pipe
”
U-Shaped Hook
1-1/32
( 1)
( 2)
False Ceiling
Mounting Plate
(Indoor Unit)
Unit: inch
Indoor Unit
Long Screw
Corner Panel
15/32
+3/16
0
Ɣ 7KHVWDQGDUGLQVWDOODWLRQGLPHQVLRQEHWZHHQWKHLQGRRUXQLWXQGHUVXUIDFHIRUWKHIDOVHFHLOLQJVXUIDFH
is 15/32 inch (+3/16 inch) or 12 mm (+ 5.0 mm). If the suspended unit is not consistently level and the
position is not correct, the decorative panel can not be installed correctly.
Ɣ ,IWKHGHFRUDWLYHSDQHOLVPRXQWHGZLWKDQRSWLRQDO¿OWHUER[DFFHVVRU\UHIHUWRWKHLQVWDOODWLRQDQG
PDLQWHQDQFHPDQXDOIRUWKH¿OWHUER[WRDVVXUHSURSHULQVWDOODWLRQ
NOTICE
NOTICE
6HFXUHO\¿WWKHFRUQHUSRVLWLRQIRUWKHUHIULJHUDQWSLSHFRQQHFWLRQDWWKHLQGRRUXQLWZLWKWKHSRVLWLRQ
stamped as
“Ref. Pipe
”
. Otherwise, if may cause air leakage.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...