1-438
Service Manual
INSTALLATION
7KHWHUPLQDOEORFN7%IRUWKHFRQWUROOHUFDEOHLVORFDWHGDVVKRZQLQWKH¿JXUHEHORZ&RQQHFWWKH
connecting cable for the IR receiver kit to terminals A and B at TB2. (There is no polarity between terminals
A and B.) The details for wiring methods can be found in the “Installation and Maintenance Manual” for the
indoor unit.
The following wiring method is an example for wall mount indoor units
NOTE:
After running the connecting cable, clamp the extra length of the connecting cable using the accessory
plastic band and place it in the electrical box.
5. Setting DIP Switches on Indoor Unit Side
Instructions for setting DIP switches for other indoor units can be found in the “Installation and Maintenance
Manual” for the indoor unit. The following DIP switch setting is an example for wall mount indoor units.
1
The factory setting of SW2 before shipment is “Wireless”. When using an IR receiver kit (CWDIRK01),
set the SW2 to “Wired”. If not doing so, the operation is not available.
2
Turn OFF the power source of the indoor and outdoor units completely before setting the DIP switch.
If not turning OFF the power, the setting becomes invalid.
3
The positions of the DIP switches are shown below.
Open the switch cover. After the DIP switch is set, re-attach the switch cover. The details for setting DIP
switches for an indoor unit can be found in the “Installation and Maintenance Manual” for the indoor unit.
< TIWM006 - 012B21S >
< TIWM015 - 024B21S >
< TIWM006 - 012B21S >
< TIWM015 - 024B21S >
< DIP Switch PCB (PCB2) >
4. Electrical Wiring
Insert the connecting
cable from the rear
of the indoor unit.
A
1
2
Electrical Box
Cover
Terminal Block for
Power Source (TB1)
Screw for
Ground Wiring Connection
Connecting Cable
for IR Receiver Kit
Fix the wires with
cable clamp.
Terminal Block for
Controller Cable (TB2)
Terminal Block for Power Source (TB1)
Screw for
Ground Wiring Connection
Connecting Cable
for IR Receiver Kit
Terminal Block for
Controller Cable (TB2)
A
B
1
Switch Cover
PCB2
Switch Cover
PCB2
DSW5
RSW2
RSW1
DSW6
DSW9
DSW2
SW1
SW2
DSW3
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...