Service Manual
1-85
INSTALLATION
9.2 Test
Run
This test run method is for the wired controller. As for other controllers, refer to Installation and Maintenance
Manual attached to each controller.
(1) Check to ensure that stop valves for high/low pressure gas, low pressure gas (only for Heat Recovery
System), and liquid of the outdoor unit are fully opened.
(In the case of combined outdoor units, check to ensure that all stop valves of the outdoor units are
fully opened.)
(2) Perform the test run of indoor units one by one sequentially, and then check the accordance of the
refrigerant piping system and the electrical wiring system. (If the multiple indoor units are operated
simultaneously, the system accordance cannot be inspected.)
(3) Perform the test run according to the following procedure. Ensure that the unit operates without any
problem.
NOTE:
In the case that two controllers (main and sub) are installed to the system, perform the test run from
the main controller.
< Test Run by Wired Controller >
(a) Press and hold “Menu” and “Back/Help” simultaneously for at least 3 seconds. The test run menu
will be displayed.
(b) Select “Test Run” by pressing “
” and press “OK”.
The test run screen will be displayed.
Ɣ
The total number of indoor units connected are displayed
on the Liquid Crystal Display (LCD). A twin combination
RQHVHWZLWKWZRLQGRRUXQLWVLVLGHQWL¿HGDV³XQLWV´
and a triple combination (of one set with three indoor
XQLWVLVLGHQWL¿HGDV³XQLWV´
NOTE:
:KHQD³XQLW´LVLGHQWL¿HGWKHDXWRDGGUHVVIXQFWLRQ
may be activated. Cancel “Test Run” mode and reset it.
Ɣ
If the indicated number is not equal to the actual number of connected indoor units, the auto-
address function is not performed correctly due to incorrect wiring, or electronic noise (EMI).
Turn OFF the power supply, and correct the wiring after checking the following areas: (Do not
repeat turning ON and OFF within 10 seconds.)
* The power supply for the indoor unit is NOT turned ON or there is incorrect wiring.
* A loose connection between indoor units or the wired controller.
* Incorrect Setting of Indoor Unit Address (The indoor unit address is overlapped.)
(c) Start the Test Run.
Ɣ
Press “
2Q2II´7KH7HVW5XQRSHUDWLRQZLOOVWDUW7KHRSHUDWLRQPRGHWKHDLUÀRZYROXPH
WKHDLUÀRZGLUHFWLRQDQGWKH7HVW5XQWLPHFDQEHVHWRQWKH7HVW5XQVFUHHQ6HOHFWWKHLWHPE\
pressing “
” and set the detail by pressing “
”.
The default setting for the Test Run time is a two-hour OFF timer.
Ɣ
Check the temperature conditions.
Unit operation cannot be performed if the conditions are out of range.
Refer to the table below for a working range.
< Example >
The cooling operation is not performed if the outdoor temperature is below 14
o
F DB (-10
o
C DB).
Cooling Operation
Heating Operation
Indoor
Temperature
Minimum
69
o
F DB/59
o
F WB (21
o
C DB/15
o
C WB)
59
o
F DB (15
o
C DB)
Maximum
89
o
F DB/73
o
F WB (32
o
C DB/23
o
C WB)
80
o
F DB (27
o
C DB)
Outdoor
Temperature
Minimum
14
o
F DB (-10
o
C DB) *
-4
o
F WB (-20
o
C WB) *
Maximum
118
o
F DB (48
o
C DB) *
59
o
F WB (15
o
C WB) *
DB: Dry Bulb, WB: Wet Bulb
*: Refer to “Page i” for details.
Test Run Screen
Back
Test Run Setting: 2 units
MODE :
COOL
SPEED :
AUTO
ON
Rtrn
Sel.
Adj.
Summary of Contents for YVAHP072B31S
Page 2: ......
Page 10: ...viii Service Manual ...
Page 16: ......
Page 17: ...Service Manual 1 1 INSTALLATION 1 Installation ...
Page 577: ...Service Manual 1 561 INSTALLATION 9 Touch Back to return to the Service Menu screen 9 ...
Page 920: ......
Page 921: ...Service Manual 2 1 OPERATION 2 Operation ...
Page 1315: ...Service Manual 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 1461: ...Service Manual 4 1 MAINTENANCE 4 Maintenance ...
Page 1728: ......
Page 1729: ...Service Manual 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 1738: ...6 10 Service Manual FIELD WORK INSTRUCTIONS 6 8 Mollier Chart for R410A ft 3 l b ...
Page 1739: ...SERVICE PARTS LIST Service Manual 7 1 7 Service Parts List ...
Page 1795: ......
Page 1796: ... 2015 Johnson Controls Inc SM 15001 ...