These instructions apply to 1

1

2

 and 3 hour rated fire 

dampers mounted in: 1) masonry, block, or stud 
walls (blades must be horizontal) and 2) concrete 
floors. Specific requirements in these instructions are 
mandatory. Dampers must be installed in accordance 
with these instructions to meet the requirements 
of UL 555.

Note: 

Fire dampers are manufactured and labeled for 

either vertical or horizontal installation. The dampers 
must be installed in accordance with labeling.

Receiving and Handling

Upon receiving dampers, check for both obvious 
and hidden damage. If damage is found, record all 
necessary information on the bill of lading and file 
a claim with the final carrier. Check to be sure that 
all parts of the shipment, including accessories, are 
accounted for.
Dampers must be kept dry and clean. Indoor storage 
and protection from dirt, dust, and the weather is 
highly recommended. Do not store at temperatures in 
excess of 100°F (38°C).

SAFETY WARNING

Improper installation, adjustment, alteration, service 
or maintenance can cause property damage, injury 
or death. Read the installation, operating, and 
maintenance instructions thoroughly before installing 
or servicing this equipment.

Table of Contents

General Information . . . . . . . . . . . . . . . . . . 2
Pre-Installation Guidelines .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   2
Preparation of Openings .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   3
Clearances Required Between Damper Sleeves & Wall/
Floor Openings.   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   4
Installing Multiple Section Assemblies.   .   .   .   .   .   .   .   .   4
Maximum Assembly Tables . . . . . . . . . . . . . . 5
Sleeve Requirements  . . . . . . . . . . . . . . . . . 5
Securing the Damper/Sleeve Assembly to Wall/Floor 
Openings .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .   6
Duct to Sleeve Connection  . . . . . . . . . . . . . . 9
Damper Commissioning and Periodic Testing.   .   .   .   .11
Damper Maintenance . . . . . . . . . . . . . . . . .11
Damper Troubleshooting.   .   .   .   .   .   .   .   .   .   .   .   .   .   .   .11

®

Curtain Fire Dampers

1

®

Document 481324

Curtain Fire Damper

DFD, DFD-150X, FD, FD-150X, SSDFD, SSFD, 

and KFD series

1

1

2

 and 3 Hour Curtain Fire Dampers

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, 
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure 
to comply with these instructions will result in voiding of the product warranty and may result in personal injury 
and/or property damage.

Содержание DFD 150 Series

Страница 1: ...tion service or maintenance can cause property damage injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Pre Installation Guidelines 2 Preparation of Openings 3 Clearances Required Between Damper Sleeves Wall Floor Openings 4 Installing Multiple Section Assemblies 4 Maximum As...

Страница 2: ... or spray painting will be performed within 5 feet of the damper 7 Caulking is not necessary nor is it allowed between the damper sleeve and the wall or floor opening annular space However caulking may be applied to the retaining angles 8 ACCESS Suitable access such that the fusible link may be removed and the damper s blade stack may be reset etc must be provided for damper inspection and servici...

Страница 3: ...nt Dow Metal Stud Framing Shown Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or smaller Metal stud only 24 in 610mm O C max Detail A A Detail A A Floor Runner Ceiling Runner Notched Piece Bent Down Metal Stud Framing Shown Ceiling Runner Detail A A Floor Runner 24 in 610mm O C Max Figure 2A Metal Stud Construction Wooden Stud Construction In metal stud construction ...

Страница 4: ...minmum of 1 in 25 mm For stainless steel dampers and stainless steel or galvanized sleeves 3 16 in per foot 5 mm per 3 m of damper width and height with a minimum clearance of 1 4 in 6 mm maximum of 2 in 51 mm These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper Although the minimum requirements are listed above for ease of installation the foll...

Страница 5: ... x 762 mm DFD 350 Vertical 36 x 36 914 mm x 914 mm Horizontal 24 x 18 610 mm x 457 mm 48 x 36 1217 mm x 914 mm 30 x 30 762 mm x 762 mm DFD 310 Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm SSDFD 150 SSDFD 350 Vertical 30 x 30 762 mm x 762 mm FD 150X Vertical or Horizontal 48 x 48 1219 mm x 1219 mm DFD 150X Vertical 36 x 36 914 mm x 914 mm Horizontal 30 x 30 762 mm x 762 mm Al...

Страница 6: ...he leg of the retaining angle on the damper sleeve shall be a minimum of 11 4 in 32 mm The leg of the retaining angle on the wall floor shall be long enough to cover the annular space and overlap the wall floor by a minimum of 1 in 25 mm Retaining Angle Attachment to Sleeve Retaining angles must be attached to the damper using one or more of the following methods of attachment refer to label on ou...

Страница 7: ...1 hour rated walls see UL Rated Wall Design for Additional Details Figure 8 Single Side Angle With Steel Stud Wall Angle Over Wallboard Stud or Runner Damper Sleeve Angle Fastener Two layers of 1 2 in UL Classified Gypsum Wallboard for 2 hour rated walls One layer for 1 hour rated walls see UL Rated Wall Design for Additional Details Figure 9 Single Side Angle With Wood Stud Wall Damper Sleeve Met...

Страница 8: ...n 178mm Type A Type B Field installed Sleeve Damper 1 4 in minimum total clearance See Section 1 Maximum 6 in Maximum 6 in Wall or floor Wall or floor Wall or floor Damper Damper Duct Duct Duct Retaining Angles See Section 4 Sleeve See Sleeve Requirements Sleeve Sleeve On types R CR factory furnished duct collar qualifies as breakaway connection See Connecting Ducts to Fire Damper Sleeve Retaining...

Страница 9: ...Precision DP1010 water base duct sealant manufactured by Design Polymerics Grey Pookie Ductmate PROseal or CL Ward S Seal in accordance with SMACNA recommendations Transverse Joints The transverse joints shown below are approved as breakaway connections A maximum of two 10 19 mm sheet metal screws on each side and on the bottom may be used The screws should be located in the center of the slip poc...

Страница 10: ...facturer s instructions Duct 3 8 in bolts in corners are optional 6 in long metal cleat or 1 16 in max thickness plastic cleat 12 in c c min 1 per side Figure 18 Manufactured Flanged System Breakaway Connections Flanged connection systems manufactured by Ductmate Durodyne Ward Nexus Radiant T 35m and MEZ are approved as breakaway connections when installed as illustrated see Figure 18 Figure 22 Me...

Страница 11: ...rated dampers utilizing a fusible link are required to be tested by removing the fusible link and allowing the damper to fully close and then manually reopening the damper Re install the fusible link Greenheck s life safety dampers shall not be tested by applying heat with uncontrollable heat sources i e heat guns torches etc as this can permanently damage the thermostat or other parts of the damp...

Страница 12: ...ves the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck com Resources Library Literature Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com Our Commitment ...

Отзывы: