ASDA-A3
Troubleshooting
Revision December, 2017
11-31
11
AL099 DSP firmware update
Trigger condition
and causes
EEPROM is not reset after DSP firmware is updated.
Checking methods
and corrective
actions
Check if the firmware is updated. Set P2.008 to 30 first and then set it to 28.
Next, cycle power on the servo drive.
How to clear the
alarm?
Set P2.008 to 30 and then 28. Cycle power on the servo drive.
AL521 Vibration elimination parameter error
Trigger condition
and causes
Condition: the value for the vibration elimination parameter (elasticity
compensation) is not appropriate.
Causes:
1. The value of vibration suppression (elasticity compensation) is
incorrect.
2. The Bode plot is in error due to other variables while the operation
system is analyzing the program.
Checking methods
and corrective
actions
Perform system analysis again and correctly set the value for the vibration
elimination parameter.
How to clear the
alarm?
1. Perform system analysis again and correctly set the value for the
vibration elimination parameter.
2. If the issue persists, please disable the vibration elimination function
P2.094 [Bit 8] & [Bit 9].
Summary of Contents for ASD-A3-0121
Page 13: ...Revision December 2017 This page is intentionally left blank...
Page 43: ...Installation ASDA A3 2 20 Revision December 2017 2 This page is intentionally left blank...
Page 105: ...Wiring ASDA A3 3 62 Revision December 2017 3 This page is intentionally left blank...
Page 187: ...Operation Mode ASDA A3 6 36 Revision December 2017 6 This page is intentionally left blank...
Page 467: ...Parameters ASDA A3 8 210 Revision December 2017 8 This page is intentionally left blank...
Page 577: ...Specifications ASDA A3 A 28 Revision December 2017 A This page is intentionally left blank...
Page 597: ...Accessories ASDA A3 B 20 Revision December 2017 B This page is intentionally left blank...
Page 603: ...4 Revision December 2017 This page is intentionally left blank...